22
Adjustable parameters
(adjustable on base unit
)
Alarm mode
(e.g. wind alarm)
1)
Factory setting
No alarm
1)
Up
Down
Anleitung_777204.book Seite 22 Montag, 14. Oktober 2002 7:37 19
23
Technical data
Bus supply
24 V / I approx. 10 mA
Ambient temperature:
Operation:
Storage:
Transport:
-5 °C to +45 °C
-25 °C to +55 °C
-25 °C to +70 °C
The device is designed for use
at a height of up to 2000 m
above sea level (MSL).
Control elements:
Programming key, manual
8 channel keys (2 per channel)
Display element:
1 red LED,
programming control
8 red status-LEDs, under the
channel keys (A - D)
1 green LED:
operation indicator
Connection:
Bus supply terminal via two 1
mm pins.
8 outer conductors via two
screw terminals for max. 2 x
1,5 mm
2
or 1 x 2,5 mm
2
Insulation voltage:
4 kV AC between bus and
230 V AC
Switching contacts
Channel A-D:
4 x changeover,
voltage-free
Nominal voltage:
AC 230 V, 50 to 60 Hz
Load:
inductive:
230 V~, 6 A, cos
ϕ
= 0,6
Switching frequency:
max. 15 per min. at nominal
load
Connected load:
motors:
230 V~, max. 1000 W
Device width:
4 depth units = approx.
70 mm
Anleitung_777204.book Seite 23 Montag, 14. Oktober 2002 7:37 19
24
EC Directives:
Complies with low voltage
directive 73/23/EEC
Complies with EMC directive
89/336/EEC
Anleitung_777204.book Seite 24 Montag, 14. Oktober 2002 7:37 19