25
Electrical connection
Caution
The switch output has a bistable relay.
Strong vibrations during transportation can
cause the switching contact of the relay
output to change to the switched on state.
When connecting to the mains, the relay
output may contain a voltage!
Note
The ambient temperature should be
observed, see "technical data".
Installation proposal:
Fig. B:
➊
Connect the red bus wire to the red
terminal (+) and the black one to the
dark grey terminal (-).
➋
The screen and the stability wire as
well as the white and yellow wires of
the bus line are not required. Insulate
and put in flush-mounted box.
➌
Wall box, DIN 49 073, Form B,
ø 60 mm
Montage
Anleitung_764194.book Seite 25 Dienstag, 15. Oktober 2002 11:21 11
26
➍
The 230 V power line (L, switched) is
connected via a 2-pin screw terminal.
Note
Follow the assembly proposal on the
following page.
When connecting the 230 V power line and
the bus line, ensure that there is a mini-
mum gap of 4 mm between the individual
insulated wires of the 230 V line and those
of the bus line.
To ensure the 4 mm minimum gap, the fol-
lowing points must be observed:
-
The input openings on opposite sides
of the installation box should be used
for the 230 V power line and the bus
line.
-
As little as possible of the casing of the
bus line should be stripped at the bus
supply terminal (casing length =
12 mm, stripped length = 6 mm).
- The enclosed flexible sleeving
➊
is
pushed over the individual 230 V lines.
Anleitung_764194.book Seite 26 Dienstag, 15. Oktober 2002 11:21 11
27
Further information on laying the bus line
can be found in the "base unit" operating
instructions and in the ZVEI/ZVEH "Build-
ing management system, Basic principles"
handbook.
Connection example:
Fig. D:
➊
Easy switching actuator for ARGUS
180 flush-mount/230/10
➋
ARGUS 180 flush-mount application
module
Assembly proposal:
Fig. E:
➊
Wall box, DIN 49 073, Form B, ø 60
mm
➋
Easy switching actuator for ARGUS
180 flush-mount/230/10
➌
Frame
➍
ARGUS 180 application module
➎
Blinding cover
The Easy switching actuator for
ARGUS flush-mount/230/10 can also
be installed without the ARGUS 180
flush-mount application module. In this
case, use the blinding cover, Art. no.
6622 .. / 6620 .. / 6621 ..
Anleitung_764194.book Seite 27 Dienstag, 15. Oktober 2002 11:21 11