13
RADIO
The radio jumper is required to program remote controls.
For programming procedure please refer to page 12, section “radio”
FREE:
No programming of remote controls possible
PLUGGED:
Programming of remote controls possible
Important: Keep jumper “RADIO” disconnected
(removed) if not in use!
STOP/8,2 KOhm
Defines whether the terminal STOP/8,2KOhm is used for an
emergency stop or a safety edge. With an emergency stop any
movement of the gate will be stopped. When used for a safety edge
the gate reverses for 1 second.
FREE:
Factory setting is 8,2KOhm. Safety edge or
8.2kOhm resistor is required.
PLUGGED:
Emergency stop required. In this case the
resistor must be removed and replaced by the
switch or a switch circuit.
OPEN/PED
Defines if a key switch opens the gate completely or partially.
FREE:
opens partially (ca. 100 -150 cm)
PLUGGED:
opens completely
Note: If the jumper OPEN/PED is plugged and timer to close is
activated as well, the functionality of the terminals “key symbol” and
“COM” changes. See section “Loop Detector” above.
PHO 2 MODE
Defines whether the second photocell is active in closing or in closing
& opening.
FREE:
active in closing
PLUGGED:
active in opening
OBSTACLE
Factory-equipped with fixed wire jumper. Cutting through increases the
operating power at the control.
CAUTION: If the jumper is severed, the gate system should be
secured with additional safety devices (contact strip, etc.).
Werkseitig mit fester Drahtbrücke ausgestattet. Durchtrennen erhöht
die Arbeitskraft an der Steuerung.
JUMPER SETTINGS