background image

 

350.135UK User Manual 

The alarm will perform self-checking of the sensor every 2 minutes. Under normal conditions 
no LEDs will flash. If the sensor fails, the amber fault LED will flash once every 2 minutes 

together with two long beeps. Also the LCD will display the error message as below, this 
indicates the alarm sensor or circuitry has failed. Please stop using the alarm immediately. 

 

 

  
The error can be caused by either loose connections on the circuitry, short circuit or sensor 

contaminated by other strong chemical fumes. Please leave the alarm in clean open air for 
24hr and see if error disappears. If the error remains, please replace alarm immediately to 

remain protected from carbon monoxide. 
 

The red alarm LED will only flash when the carbon monoxide count reaches an alert level and 
activates the alarm. Under normal conditions the carbon monoxide count should be below 

25ppm. Therefore when the count is below 25, the LCD will only display 0ppm and the 
temperature reading in a 30 second cycle. 

 

 

 

To meet EN50291 standards, the alarm will activate within following time limits when different 
critical CO level is met. 

CO count (parts per million) 

Alarm response time 

33ppm 

120 mins + 

55ppm 

Within 60 to 90 mins 

110ppm 

Within 10 to 40 mins 

330ppm 

Within 3 mins 

When the alarm is activated the frequency of the sound will increase with the concentration, 
when the concentration of the carbon monoxide reaches above 550ppm the alarm will sound 

continuously with the LCD displaying “Hco” (high carbon monoxide) as below. This indicates a 
dangerously high concentration of carbon monoxide present and all persons must evacuate 

the building 

IMMEDIATELY

.  

 

 

When alarm is activated it can be temporarily silenced by pressing the TEST button, the alarm 
LED will remain flashing to indicate the presence of high concentration of carbon monoxide. 

ONLY silence the alarm when you are 100% sure that the source of the carbon monoxide has 
been dealt with. 

Summary of Contents for COD100B

Page 1: ...COD100B Carbon Monoxide Alarm Item ref 350 135UK User Manual...

Page 2: ...ntilation is lacking Please read through the following manual carefully on how to correctly install operate and maintain the device and also for action to be taken in the event of detection of dangero...

Page 3: ...level It is advised to locate the alarm near the potential source of CO such as rooms with a boiler fireplace or gas oven For optimum detection the alarm needs to be installed at least 1 5m above the...

Page 4: ...roundings When the alarm is powered the green power LED will flash once every 45 seconds to indicate it is working When the working voltage drops below 3 5V the alarm will beep when the power LED flas...

Page 5: ...d be below 25ppm Therefore when the count is below 25 the LCD will only display 0ppm and the temperature reading in a 30 second cycle To meet EN50291 standards the alarm will activate within following...

Page 6: ...o all active gas including chemical cleaners Always perform a manual test after cleaning to ensure the alarm is working normally Also the battery compartment needs to be checked on regular basis for s...

Page 7: ...an open door or window for fresh air Do a head count to check all persons are accounted for 3 DO NOT re enter the premises or move away from the door window until the alarm has stopped 4 Call the UK E...

Page 8: ...led appliances in enclosed spaces Do not use fueled generators in enclosed space Paraffin flueless heaters should not be used in a bedroom or an enclosed space Ensure all flues chimneys or other venti...

Reviews: