background image

 

350.135UK User Manual 

 

Installation: 

After finding an appropriate location, the wall bracket can be screwed onto the wall using the 
supplied hardware. Alternatively it can be stuck on using a pad sticker or just rested on top of 

a unit.  
To mount the bracket using hardware, use the 

mounting plate as a guide to mark the two holes. 
Drill these holes 6mmØ , 30mm deep. Insert the 

plugs into the hole and screw the bracket on, 
ensuring the raised side is facing outward and is 

pointing upward correctly as shown.   
 

Push the back of the alarm against the bracket and 
slide down until it clicks to lock in place. The 

battery compartment has latches that rise up to 
prevent the alarm being installed without batteries, 
therefore please ensure the batteries are inserted 

before installing the alarm.   
 

Operation: 

The LCD screen and LEDs on the front of the alarm give vital information of the working 

condition of the alarm and important ambient readings of the surroundings. 
 

When the alarm is powered, the green power LED will flash once every 45 seconds to indicate 
it is working. When the working voltage drops below 3.5V, the alarm will beep when the 

power LED flashes. This indicates the battery power is insufficient; please replace battery as 
soon as possible. On the LCD display, the battery status is also shown constantly: 

 

 Indicates batteries are at full capacity and alarm is working with sufficient power. 
 Indicates batteries have sufficient capacity and alarm is working with sufficient power. 
 Indicates batteries capacity is getting low but alarm still has sufficient power. 
 Indicates batteries are critically low and alarm is working on the minimum required 

power and requires replacement as soon as possible in order to keep the alarm functional. 
 

It is recommend to manually perform testing once a week. To perform a manual test, simply 
press the test button for 1 second and the alarm will enter test mode. All three LEDs will flash 

once and alarm will sound 2 cycles of 4. The LCD screen will read “---“ to indicate it’s testing. 
 

 

 

All LEDs and the LCD display should resume back to normal after a few seconds. 

 

Summary of Contents for COD100B

Page 1: ...COD100B Carbon Monoxide Alarm Item ref 350 135UK User Manual...

Page 2: ...ntilation is lacking Please read through the following manual carefully on how to correctly install operate and maintain the device and also for action to be taken in the event of detection of dangero...

Page 3: ...level It is advised to locate the alarm near the potential source of CO such as rooms with a boiler fireplace or gas oven For optimum detection the alarm needs to be installed at least 1 5m above the...

Page 4: ...roundings When the alarm is powered the green power LED will flash once every 45 seconds to indicate it is working When the working voltage drops below 3 5V the alarm will beep when the power LED flas...

Page 5: ...d be below 25ppm Therefore when the count is below 25 the LCD will only display 0ppm and the temperature reading in a 30 second cycle To meet EN50291 standards the alarm will activate within following...

Page 6: ...o all active gas including chemical cleaners Always perform a manual test after cleaning to ensure the alarm is working normally Also the battery compartment needs to be checked on regular basis for s...

Page 7: ...an open door or window for fresh air Do a head count to check all persons are accounted for 3 DO NOT re enter the premises or move away from the door window until the alarm has stopped 4 Call the UK E...

Page 8: ...led appliances in enclosed spaces Do not use fueled generators in enclosed space Paraffin flueless heaters should not be used in a bedroom or an enclosed space Ensure all flues chimneys or other venti...

Reviews: