Mercury Security © 2015 

EP1502 

DOC  10107-0031  

REV 1.06 

 Page   8 

Reader Interface: 

Power: 

12 Vdc ± 10 % regulated, 180 mA maximum each reader 

(jumper selectable) 

(input voltage (VIN) must be greater than 20 Vdc) 
or 
12 to 24 Vdc ± 10 % (input voltage passed through), 180 mA maximum each 
reader 

Data Inputs: 

 

TTL compatible, F/2F or 2-wire RS-485 

LED Output: 

TTL levels, high>3 V, low<0.5 V, 5 mA source/sink maximum 

Buzzer Output: 

Open collector, 12 Vdc open circuit maximum, 40 mA sink maximum 

Cable requirements: 

Power: 

1 twisted pair, 18 AWG 

Ethernet: 

CAT-5, minimum 

RS-485: 

(I/O Device Port): 1 twisted pair with drain wire and shield, 24 AWG, 4,000 ft. (1,219 m) max. 
(Reader Port): 

1 twisted pair with drain wire and shield, 24 AWG, 2,000 ft. (610 m) max. 

RS-232: 

3 or 5-conductor, 24 AWG, 25 ft. (7.6 m) maximum 

Alarm Input: 

1 twisted pair, 30 ohms maximum 

Mechanical: 

Dimension: 

8 in. (203.2 mm) W x 6 in. (152.4 mm) L x 1 in. (25 mm) H 

Weight: 

9 oz. (255 g) nominal, board only  

Environmental: 

Temperature: 

-55 to +85 °C, storage 

0 to +70 °C, operating 

Humidity: 

5 to 95 % RHNC 

 

 

Warranty 

Mercury Security warrants the product is free from defects in material and workmanship under normal use 
and  service  with  proper  maintenance  for  one  year  from  the  date  of  factory  shipment.    Mercury  Security 
assumes  no  responsibility  for  products  damaged  by  improper  handling  or  installation.    This  warranty  is 
limited to the repair or replacement of the defective unit. 

There  are  no  expressed  warranties  other  than  set  forth  herein.    Mercury  Security  does  not  make,  nor 
intends,  nor  does  it  authorize  any  agent  or  representative  to  make  any  other  warranties,  or  implied 
warranties, and expressly excludes and disclaims all implied warranties of merchantability or fitness for a 
particular purpose. 

Returns must be accompanied by a Return Material Authorization (RMA) number obtained from customer 
service, and prepaid postage and insurance. 

Liability

 

The  Interface  should  only  be  used  to  control  exits  from  areas  where  an  alternative  method  for  exit  is 
available.    This  product  is  not  intended  for,  nor  is  rated  for  operation  in  life-critical  control  applications.  
Mercury Security is not liable under any circumstances for loss or damage caused by or partially caused 
by the misapplication or malfunction of the product.  

Mercury Security’s liability does not extend beyond the 

purchase price of the product. 

 

Summary of Contents for EP1502

Page 1: ...d that may be used for monitoring the door contacts exit push buttons and alarm contacts Input circuits may be configured as unsupervised or supervised The EP1502 requires 12 to 24 Vdc for power 2 EP1...

Page 2: ...lly Open Contact TB5 2 IN4 TB11 2 C Common TB5 3 Input 3 IN3 TB11 3 NC Normally Closed Contact TB5 4 IN3 TB11 4 Out 4 NO Normally Open Contact TB6 1 Input 6 IN6 TB11 5 C Common TB6 2 IN6 TB11 6 NC Nor...

Page 3: ...wing purposes Erase all configuration and cardholder database sanitize board Update OEM default parameters after OEM code has been changed Recover from database corruption causing EP1502 board to cont...

Page 4: ...ort supports a reader with TTL D1 D0 Clock Data F 2F or 2 wire RS 485 signaling Power to the readers is selectable 12 Vdc VIN must be greater than 20 Vdc or power is passed through PASS from the input...

Page 5: ...e standard supervised circuit requires 1k ohm 1 resistors and should be located as close to the sensor as possible Custom end of line EOL resistances may be configured via the host software Grounded a...

Page 6: ...tallation the user accounts to the web configuration page should be created with secure passwords and that all DIP switches are in the off position for the normal operating mode The EP1502 is shipped...

Page 7: ...le See Note 1 IN3 Input IN3 Status OFF Inactive ON Active Flash Trouble See Note 1 IN4 Input IN4 Status OFF Inactive ON Active Flash Trouble See Note 1 IN5 Input IN5 Status OFF Inactive ON Active Flas...

Page 8: ...ee from defects in material and workmanship under normal use and service with proper maintenance for one year from the date of factory shipment Mercury Security assumes no responsibility for products...

Reviews: