Mercury Security © 2015
EP1502
DOC 10107-0031
REV 1.06
Page 7
Running:
After initialization is complete, the LEDs have the following meanings: At power up, LEDs 2
through 6 are turned ON then OFF in sequence.
LED
DESCRIPTION
1
Off-Line / On-Line and Battery Status
Off-Line = 20% ON, On-Line = 80% ON
Double Flash if Battery is Low
2
Host Communication Activity (Ethernet or Serial Port 1)
3
Internal SIO Communication Activity
TMP
External SIO Communication Activity
FLT
Unassigned
R1
Reader 1:
Clock/Data or D1/D0 Mode: Flashes when Data is Received, Either Input
F/2F Mode: Flashes when Data/Acknowledgment is Received
RS-485 Mode: Flashes when Transmitting Data
R2
Reader 2:
Clock/Data or D1/D0 Mode: Flashes when Data is Received, Either Input
F/2F Mode: Flashes when Data/Acknowledgment is Received
RS-485 Mode = Flashes when Transmitting Data
D16
Flashes with Host Communication (Ethernet Port 0)
YEL
Ethernet Speed: OFF = 10Mb/S, ON = 100Mb/S
GRN
OFF = No Link, ON = Good Link, Flashing = Ethernet Activity
IN1
Input IN1 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
IN2
Input IN2 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
IN3
Input IN3 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
IN4
Input IN4 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
IN5
Input IN5 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
IN6
Input IN6 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
IN7
Input IN7 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
IN8
Input IN8 Status: OFF = Inactive, ON = Active, Flash = Trouble. See Note 1.
K1
Relay K1: ON = Energized
K2
Relay K2: ON = Energized
K3
Relay K3: ON = Energized
K4
Relay K4: ON = Energized
Note 1: If this input is defined, every three seconds the LED is pulsed to its opposite state for 0.1
seconds, otherwise, the LED is off.
13. Specifications:
The interface is for use in low voltage, Class 2 Circuits only.
The installation of this device must comply with all local fire and electrical codes.
Primary Power:
12 to 24 Vdc ± 10 %, 500 mA maximum (reader current not included)
Memory and Clock
Backup Battery:
3 Volt Lithium, type BR2325, BR2330 or CR2330
Host Communication:
Ethernet: 10-BaseT/100Base-TX, and RS-232: 9,600 to 115,200 bps
Serial I/O Device
2-wire RS-485: 2,400 to 115,200 bps
Inputs:
Eight unsupervised/supervised, standard EOL: 1k/1k ohm, 1%, ¼ watt
Two unsupervised dedicated for cabinet tamper and UPS fault monitoring
Outputs:
Four relays: Form-C, 5 A @ 30 Vdc, resistive