background image

 

8/15 

 

 

 

Type SO safety mesh 

made of galvanized steel sheet and galvanized wire mesh. Powder-coated in standard, or galvanized on 
custom  order.  The  fitting  protects  the  fan  from  ingress  of  foreign  bodies.  Periodically  check  that  the 
safety mesh is clean and clean it when necessary. 

Type SO safety mesh 

 
 

 
 

Fan - Type 

Type 

[mm] 

[mm] 

~B 

[mm] 

~h 

[mm] 

C  

nxd 

[mm] 

[kg] 

mcr Pasat 31 

SO-31 

315 

385 

356 

45 

8x9.6 

1.1 

mcr Pasat 35 

SO-35 

355 

395 

425 

45 

8x9.6 

1.2 

mcr Pasat 40 

SO-40 

400 

438 

470 

30 

12x9.6 

1.3 

mcr Pasat 50 

SO-50 

500 

541 

570 

30 

12x9.6 

1.7 

mcr Pasat 63 

SO-63 

630 

674 

710 

22.5  16x10.5 

2.5 

mcr Pasat 71 

SO-71 

710 

751 

790 

22.5  16x10.5 

2.9 

 

 

Type KS-V automatic non-return damper 

the  damper  housing  is  made  of  galvanized  steel  sheet.  Powder-coated  in  standard,  or  galvanized  on 
custom order.

 

The damper blade is made of aluminium sheet. Type KS-V automatic non-return dampers 

are installed to prevent air circulation and heat losses when the fan is in standstill. The automatic non-
return damper is intended for vertical installation [with the damper blade axis is  horizontal]. 
The damper needs precise levelling to  operate correctly. 

Type KS-V automatic non-return damper 

 
 

 

 

Fan - Type 

Type 

[mm] 

A [mm] 

[mm] 

[mm] 

C  

nxd 

[mm] 

[kg] 

mcr Pasat 31 

KS-V-31 

315 

385 

356 

220 

45 

8x9.6 

5.7 

mcr Pasat 35 

KS-V-35 

355 

425 

395 

240 

45 

8x9.6 

6.6 

mcr Pasat 40 

KS-V-40 

400 

470 

438 

250 

30 

12x9.6 

7.6 

mcr Pasat 50 

KS-V-50 

500 

570 

541 

320 

30 

12x9.6 

11.3 

mcr Pasat 63 

KS-V-63 

630 

710 

674 

360 

22.5  16x10.5 

16.2 

mcr Pasat 71 

KS-V-71 

710 

790 

751 

430 

22.5  16x10.5 

20.8 

 

Type WS service switch

 

Designed to cut-offelectric power from the fan when inspection or maintenance work is necessary. Each 
service switch features an auxiliary contact which indicates the power off position. 

 

Type WS service switch 

 
 

 
 

Type 

A [mm]  B [mm]  E [mm]  F [mm]  H [mm] 

nxd [mm] 

[V] 

[A] 

Glands [D] 

Comments 

WS-16/3 

90 

90 

67 

48 

95 

4x4 

690 

16 

M20[x4] 

3-pole 

WS-16/6 

90 

90 

67 

48 

95 

4x4 

690 

16 

M20[x4] 

6-pole 

WS-32/6 

116 

100 

90 

52 

108 

4x4 

690 

32 

M25[x4] 

6-pole 

WS-63/6 

170 

155 

105 

95 

185 

4x6 

690 

63 

M25/M32[x4] 

6-pole 

Summary of Contents for mcr Pasat

Page 1: ...ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 48 58 341 42 45 tel fax 48 58 341 39 85 TECHNICAL MANUAL Roof smoke exhaust fan mcr Pasat Version Pasat 19 06 27 3 FIRE VENTILATION SYSTEMS ...

Page 2: ...n 6 5 3 Dimensions 6 5 4 Accesories 7 6 IDENTIFICATION MARKING 9 7 INSTALLATION 9 7 1 Pre assembly inspection 9 7 2 Location and assembly 9 7 3 Electrical connections 11 7 4 Commissioning 12 8 TRANSPORT STORAGE CONDITIONS 12 9 SAFETY MANUAL 12 10 MAINTENANCE SERVICING 13 11 WARRANTY TERMS CONDITIONS 13 VENTILATOR MEASUREMENT REPORT 15 Technical Manual designations available option unavailable opti...

Page 3: ...ISO 12100 1 2005 Safety of machinery Basic concepts general principles for design Part 1 Basic terminology methodology PN EN ISO 12100 2 2005 Safety of machinery Basic concepts general principles for design Part 2 Technical principles PN EN 60204 1 2001 Safety of machinery Electrical equipment of machines Part 1 General requirements The smoke exhaust fan design also meets the state of the art in t...

Page 4: ...tion of persons from the area on fire protect the building structure and its furnishing from high temperature facilitate fire fighting and inhibit spreading of fire to adjacent fire zones The available versions include single functional with single speed motors two functional i e for general and fire ventilation and with two speed motors The fans can be installed outdoors on suitable consoles roof...

Page 5: ...0o C for 120 minutes Class F600 fire resistance at 600o C for 60 minutes 4 3 Versions Single speed single functional fans Two speed two functional fans 5 DESIGN AND OPERATING PRINCIPLE 5 1 Design ______________________________________________________________________ 1 Fan base 2 Cooling duct 3 External housing 4 Motor housing 5 Inlet port 6 Motor base 7 Radial rotor 8 Electric box service switch o...

Page 6: ...________________________________________ The single functional fans do not run in standby When 3 phase voltage is present on the electric box terminals the fan is started and running The two functional fans run at low speed RPM to handle general ventilation under normal conditions When the fan receives an alarm signal it automatically starts running with the second speed which is higher than the f...

Page 7: ...It acts as a vibration damper It is also used to compensate for thermal elongation The fan integrated in a ventilation system should feature the flexible joint on the suction side Type KD flexible joint Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 35 KD 31 315 385 356 150 45 8x9 6 1 0 mcr Pasat 35 KD 35 355 425 395 150 45 8x9 6 1 1 mcr Pasat 40 KD 40 400 470 438 150 30 12x9 6 1 3 mcr ...

Page 8: ...heat losses when the fan is in standstill The automatic non return damper is intended for vertical installation with the damper blade axis is horizontal The damper needs precise levelling to operate correctly Type KS V automatic non return damper Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 31 KS V 31 315 385 356 220 45 8x9 6 5 7 mcr Pasat 35 KS V 35 355 425 395 240 45 8x9 6 6 6 mcr P...

Page 9: ..._________________________________________ Locate the mcr Pasat smoke exhaust fan outdoor and beyond the fire zone The equipment installation orientation must be horizontal i e with the motor axis in the vertical at a minimum height of 250 mm above the roof plane Prior to installation verify the load bearing capacity of the roof structure on which the equipment is to be located Prepare and secure a...

Page 10: ...ust fan or other components of the assembly The ventilation duct must be supported by independent bearing slings Secure the smoke exhaust fan suction intake with type SO safety mesh When installing the smoke exhaust fan secure the installation site and all involved structures and prepare passage and access ways for all personnel not involved in the installation The smoke exhaust fan must be assure...

Page 11: ... inadvertent shutdown of the smoke exhaust fan with the sole exception of the fan dedicated service switch with remote indication of current circuit switching The smoke exhaust fan control cabinets must be powered directly from mail switchboards with guaranteed uninterrupted power supply even if the entire building is cut off from the power grid If a main fireman s switch is installed to isolate p...

Page 12: ...ases corrosive vapours and other aggressive chemical emissions detrimental to insulation parts and structural components of the fan and or its motor the maximum relative humidity is 80 at 20 C the ambient temperature does not exceed the range of 20ºC to 40 ºC no vibrations are present 9 SAFETY MANUAL________________________________________________ Read and understand this Technical Manual before c...

Page 13: ...85 from 8 AM to 4 PM Mo Fri 11 WARRANTY TERMS CONDITIONS ___________________________ 1 MERCOR SA grants 12 months of warranty for the equipment quality from the date of purchase unless the sales contract states otherwise 2 Submit each warranty claim to MERCOR SA in 7 days from the date of discovery of a warranty eligible defect 3 Submit warranty claims by calling at tel 48 58 341 42 45 by fax 48 5...

Page 14: ...ressive external influence specifically chemical or biological in nature or when the origin of which is related to the production processing or activity carried out within the facility protected by the equipment or in its direct vicinity Wearing parts and consumables e g gaskets seals unless they have defects of workmanship and or material Damage caused by improper transport handling unloading and...

Page 15: ...f the equipment MEASUREMENT RESULTS A U1 V1 W1 U2 V2 W2 NOTES Full name of the measuring technician Date measured Signature Return this Report immediately after completion of measurements to MERCOR SA Fire Ventilation Systems Ul Grzegorza z Sanoka 2 80 408 Gdańsk and not later than in 8 weeks from the date of equipment purchase equivalent to the date of the VAT sales invoice THE EQUIPMENT WARRANTY...

Reviews: