10. MAINTENANCE & SERVICING____________________________________ 

The equipment from Mercor SA require periodic technical inspection and maintenance at least every 12 
months  throughout  its  operating  life,  i.e.  during  the  warranty  and  post-warranty  period.  Inspection  and 
maintenance  may  only  be  carried  out  by  the  manufacturer  or  contractors  authorised  by  Mercor  SA  to 
service its products. 
Regular service inspections of fire protection equipment is mandatory in Poland according to § 3 Section 
3  of  the  Polish  Regulation  of  the  Ministry  of  the  Interior  and  Administration  of  7  June  2010  on  the  fire 
protection  of  buildings,  other  structures  and  areas  (Polish  Journal  of  Laws,  Year  2010,  No.  109  Item 
719).  
Do these recommended actions in the inspection intervals: 

  Check the electrical connections, especially for all mechanical damage. 

  Check the equipment casing, especially for all mechanical damage. 

  Check for any obstructions to proper performance of the equipment. 

To  facilitate  the  activities  under  service  inspection,  servicing  and  warranty  claim  response,  e.g.  visual 
inspection  or  repairs,  the  equipment  user/operator  shall  provide  physical  access  to  the  equipment  by 
removing  thermal  insulation,  suspended  ceiling,  and  other  installations,  as  required  and  applicable  to 
warrant unobstructed access. 
In the case of roof mounted equipment, provide access to the area (via ladders or elevated platforms). 
If  the  equipment  is  only  operated  for  smoke  exhaust  during  fire,  test  run  it  for  ca.  10  minutes  every  3 
months. 
 
Refer  all  matters  related  to  technical  inspection,  maintenance  and  servicing  of  this  equipment  to  the 
Mercor SA Service Department, [email protected], tel. +48 58 341 42 45 ext. 170, fax: +48 58 341 
39 85, from 8 AM to 4 PM (Mo-Fri). 

 

 

11. WARRANTY TERMS & CONDITIONS 

___________________________ 

1.  “MERCOR” SA grants 12 months of warranty for the equipment quality from the date of purchase, 

unless the sales contract states otherwise. 

2.  Submit each warranty claim to “MERCOR” SA in 7 days from the date of discovery of a warranty 

eligible defect 

3.  Submit warranty claims by calling at: tel. +48 58 341 42 45, by fax: +48 58 341 39 85, by e-mail: 

[email protected]  or  by  traditional  mail:  “MERCOR”  SA,  ul.  Grzegorza  z  Sanoka  2,  80-
408 Gdańsk, Poland. 

4.  If physical defects of equipment are found during the warranty period, “MERCOR” SA warrants and 

represents  to  remove  them  in  shortest  possible  time from  serving the  written  warranty  claim  with 
the proof of purchase or sales contract, subject to Item 10. 

5.  “MERCOR”  SA  has  the  right  to  extend  the  time  of  repair  if  the  defect  removal  is  complicated  or 

requires purchase of custom components or spare parts. 

6.  The  warranty  liability  only  covers  all  defects  arising from  causes  present  in  the  equipment  at  the 

date of sale. 

7.  Defects caused by improper operation or otherwise as listed in Item 10 herein, the buyer / warranty 

beneficiary will be charged with the costs of their removal. 

8.  Condition for rectifying defects is that the applicant makes the site/localisation where devices are 

installed available, in particular, ensuring: the lift in the case of devices mounted at a height above 
3m,  free  access  to  the  rooms  where  the  devices  were  installed  and  necessary  revisions, 
dismantling  thermal  insulation,  disassembling  suspended  ceilings,  disassembling  other 
installations, if they prevent free access to the device. 

9.  If  the  device  can  not  be  repaired  at  the  place  of  its  installation,  "MERCOR"  SA  reserves  the 

necessity of its disassembly, possible delivery to the address indicated by "MERCOR" SA and re-
assembly. The cost of this operation lies with the buyer / holder of the guarantee. 

Summary of Contents for mcr Pasat

Page 1: ...ul Grzegorza z Sanoka 2 80 408 Gdańsk tel 48 58 341 42 45 tel fax 48 58 341 39 85 TECHNICAL MANUAL Roof smoke exhaust fan mcr Pasat Version Pasat 19 06 27 3 FIRE VENTILATION SYSTEMS ...

Page 2: ...n 6 5 3 Dimensions 6 5 4 Accesories 7 6 IDENTIFICATION MARKING 9 7 INSTALLATION 9 7 1 Pre assembly inspection 9 7 2 Location and assembly 9 7 3 Electrical connections 11 7 4 Commissioning 12 8 TRANSPORT STORAGE CONDITIONS 12 9 SAFETY MANUAL 12 10 MAINTENANCE SERVICING 13 11 WARRANTY TERMS CONDITIONS 13 VENTILATOR MEASUREMENT REPORT 15 Technical Manual designations available option unavailable opti...

Page 3: ...ISO 12100 1 2005 Safety of machinery Basic concepts general principles for design Part 1 Basic terminology methodology PN EN ISO 12100 2 2005 Safety of machinery Basic concepts general principles for design Part 2 Technical principles PN EN 60204 1 2001 Safety of machinery Electrical equipment of machines Part 1 General requirements The smoke exhaust fan design also meets the state of the art in t...

Page 4: ...tion of persons from the area on fire protect the building structure and its furnishing from high temperature facilitate fire fighting and inhibit spreading of fire to adjacent fire zones The available versions include single functional with single speed motors two functional i e for general and fire ventilation and with two speed motors The fans can be installed outdoors on suitable consoles roof...

Page 5: ...0o C for 120 minutes Class F600 fire resistance at 600o C for 60 minutes 4 3 Versions Single speed single functional fans Two speed two functional fans 5 DESIGN AND OPERATING PRINCIPLE 5 1 Design ______________________________________________________________________ 1 Fan base 2 Cooling duct 3 External housing 4 Motor housing 5 Inlet port 6 Motor base 7 Radial rotor 8 Electric box service switch o...

Page 6: ...________________________________________ The single functional fans do not run in standby When 3 phase voltage is present on the electric box terminals the fan is started and running The two functional fans run at low speed RPM to handle general ventilation under normal conditions When the fan receives an alarm signal it automatically starts running with the second speed which is higher than the f...

Page 7: ...It acts as a vibration damper It is also used to compensate for thermal elongation The fan integrated in a ventilation system should feature the flexible joint on the suction side Type KD flexible joint Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 35 KD 31 315 385 356 150 45 8x9 6 1 0 mcr Pasat 35 KD 35 355 425 395 150 45 8x9 6 1 1 mcr Pasat 40 KD 40 400 470 438 150 30 12x9 6 1 3 mcr ...

Page 8: ...heat losses when the fan is in standstill The automatic non return damper is intended for vertical installation with the damper blade axis is horizontal The damper needs precise levelling to operate correctly Type KS V automatic non return damper Fan Type Type D mm A mm B mm L mm C nxd mm m kg mcr Pasat 31 KS V 31 315 385 356 220 45 8x9 6 5 7 mcr Pasat 35 KS V 35 355 425 395 240 45 8x9 6 6 6 mcr P...

Page 9: ..._________________________________________ Locate the mcr Pasat smoke exhaust fan outdoor and beyond the fire zone The equipment installation orientation must be horizontal i e with the motor axis in the vertical at a minimum height of 250 mm above the roof plane Prior to installation verify the load bearing capacity of the roof structure on which the equipment is to be located Prepare and secure a...

Page 10: ...ust fan or other components of the assembly The ventilation duct must be supported by independent bearing slings Secure the smoke exhaust fan suction intake with type SO safety mesh When installing the smoke exhaust fan secure the installation site and all involved structures and prepare passage and access ways for all personnel not involved in the installation The smoke exhaust fan must be assure...

Page 11: ... inadvertent shutdown of the smoke exhaust fan with the sole exception of the fan dedicated service switch with remote indication of current circuit switching The smoke exhaust fan control cabinets must be powered directly from mail switchboards with guaranteed uninterrupted power supply even if the entire building is cut off from the power grid If a main fireman s switch is installed to isolate p...

Page 12: ...ases corrosive vapours and other aggressive chemical emissions detrimental to insulation parts and structural components of the fan and or its motor the maximum relative humidity is 80 at 20 C the ambient temperature does not exceed the range of 20ºC to 40 ºC no vibrations are present 9 SAFETY MANUAL________________________________________________ Read and understand this Technical Manual before c...

Page 13: ...85 from 8 AM to 4 PM Mo Fri 11 WARRANTY TERMS CONDITIONS ___________________________ 1 MERCOR SA grants 12 months of warranty for the equipment quality from the date of purchase unless the sales contract states otherwise 2 Submit each warranty claim to MERCOR SA in 7 days from the date of discovery of a warranty eligible defect 3 Submit warranty claims by calling at tel 48 58 341 42 45 by fax 48 5...

Page 14: ...ressive external influence specifically chemical or biological in nature or when the origin of which is related to the production processing or activity carried out within the facility protected by the equipment or in its direct vicinity Wearing parts and consumables e g gaskets seals unless they have defects of workmanship and or material Damage caused by improper transport handling unloading and...

Page 15: ...f the equipment MEASUREMENT RESULTS A U1 V1 W1 U2 V2 W2 NOTES Full name of the measuring technician Date measured Signature Return this Report immediately after completion of measurements to MERCOR SA Fire Ventilation Systems Ul Grzegorza z Sanoka 2 80 408 Gdańsk and not later than in 8 weeks from the date of equipment purchase equivalent to the date of the VAT sales invoice THE EQUIPMENT WARRANTY...

Reviews: