mcr FIND WING
fire protection cut-off damper
MERCOR SA –
The company reserves the right to modify and change the document. Version: mcr FID WING 21.08.02.1
9/15
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar*
5. Rigid walls
6. The 12,5mm drywall board
band
7. Mortar or mineral wool *
X Wall thickness
installation of the mcr FID WING damper in rigid walls for EIS60
* Recommended installation of the damper in a dry system is based on wool of min. 100 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.
1. mcr FID WING damper
2. Insulating band
3. Ventilation duct
4. Mortar*
5. Rigid walls
6. The 12,5mm drywall board
band
7. Mortar or mineral wool *
X Wall thickness
installation of the mcr FID WING damper in rigid walls for EIS120
* Recommended installation of the damper in a dry system is based on wool of min. 100 kg / m3 with A1 non-
flammability class. The recommended installation of the damper in a wet system is based on a plaster or cement-
based mortar.
The manufacturer allows the use of other materials with parameters that confirm and ensure the appropriate class of
fire resistance for the applied method of assembly.