Smoke and Heat Exhaust Control Unit mcr 9705
– User Instruction Manual
Strona 9 z 24
on the jumpers H6 and H5
(Pic. 3 item 46 and item 47
table of
settings below)
,
SW1-5 ON
-
Pressing the button
once causes the vent to open for the time
specified by appropriate settings on the H6 and H5 jumpers
(Pic. 3 item 46 and item 47).
Pic. 4
Sample ventilation button and a two-position key switch
.
If the system is additionally equipped with a key switch
(Pic. 4),
setting the ignition
switch in the "1" position activates the "hatch" mode in place of the "ventilation"
mode. When "hatch" mode is active:
-
the weather station’s displays don’t cause vent’s closing,
- it is not possible to close the vent with the ventilation button
,
- the vent opens, just like in "ventilation" mode, by pressing the ventilation button,,
- the time of opening the damper depends on the settings on the H6 and H5 jumpers,
the vents:
Jumper:
Condition:
Opening time in:
„ventilation mode”
„ventilation mode”
H6
-
depending on how long ventilating button is pressed
down (maximum 140 seconds)
H5
-
H6
present*
20 s
45 s
H5
present*
H6
-
15 s
40 s
H5
present
H6
present
10 s
35 s
H5
-
*default settings
NOTE!!
The ventilation function is inactive when an emergency alarm is
active or if
there’s mains power outage!