Smoke and Heat Exhaust Control Unit mcr 9705
– User Instruction Manual
Strona 6 z 24
Pic. 3 Interior view of the control unit.
At the bottom of the control unit module there is a multi-function button:
No. Description
Function
24
RESET
in the alarm state - deleting the alarm and closing the
vent
in the state of supervision - closing the vent
Press
the button for at least 1 second!
To the left of the RESET button there is an eight-position switch SW1 (27),
designed
to set the functions of the control unit:
Switch position
Function
SW1-1
Disconnection of the actuator line
SW1-2
Disconnection of the sensor line
SW1-3
Disconnection of the ROP pushbutton line
SW1-4
Disconnection of the in/out relay contacts
SW1-5
Full opening of the vents during non-emergency ventilation in
in "ventilation" and "hatch" mode
SW1-6
Activation of the mode
– “door’s control”
SW1-5
+
SW1-6
Enabling the electric locking drive/ activating alarm boxes
------------------------------------------------------------------------
Activation of automation mode in mcr PROSMOKE CE/CE1
curtain (for control panels with the "curtain" option)
SW1-7
-
SW1-8
Disabling the autoreset function
Note: the default setting for SW1-1 to SW1-7
– is OFF position,
SW1-8
– is ON position.