Page 9
•
CHANGE UPPER RANGE VALUE
1. Access the menu by pressing the Zero+Span buttons.
2. Move to the next menu by pressing the Zero button until
the 1 TRIM message appears.
3. Press the Span button until the 2 SETUP message appears.
4. Press the Span button until the 21 Unit message appears.
5. Press the Zero button until the 22 U-RNG message appears.
6. Press the Span button until the Zero Adjustment
message appears.
•
CHANGE LOWER RANGE VALUE
1. Access the menu by pressing the Zero+Span buttons.
2. Move the to next menu by pressing the Zero button until
the 1 TRIM message appears.
3. Press the Span button until the 2 SETUP message appears.
4. Press the Span button until the 21 Unit message appears.
5. Press the Zero button until the 22 U-RNG message appears.
6. Press the Zero button until the 23 L-RNG message appears.
7. Press the Span button until the Change Lower Range
Value message appears.
1. Decimal Place
1. Access the menu by pressing the Zero+Span buttons.
2. Move to the next menu by pressing the Zero button until
the 1 TRIM message appears.
3. Press the Span button until the 2 SETUP message appears.
4. Press the Span button until the 3 LCD message appears.
5. Press the Span button until the 31 DEC-PL message
appears.
6. Press the Span button until the Decimal Place
message appears, the decimal place will appear on the
second line of the LCD as follows.
7. The first line on the LCD will display 0.0.
8. The Decimal Place can be changed by pressing the Zero
button. Save the setting by pressing the Span button
after the decimal place has been selected.
9. The set value will display the PV value and
Engineering value.
10. The LCD will display LCD_OV and the saved Unit when
the pressure is over or under a set value.
3.10 Shop Commissioning using HHT
The 3100 Pressure Transmitter can be commissioned using an HHT
before or after installation.
▲ Connect an HHT (HART
®
HANDHELD Communicator) across the
COMM pins for HART
®
communication. The TEST pin connections
can be used for connecting a multimeter to measure the output
current directly from the transmitter. Since the 3100 is a two wire
loop powered transmitter, it requires an external loop power supply
(11.9V to 45VDC) to enable HART
®
communication. Any HART
®
communication via HHT (or PC based configurator) requires a
minimum 250 ~ 550 (max) ohm loop resistance.
Display
AUTO
5-0
4-1
3-2
2-3
1-4
Explanation
Target value will be displayed
automatically
No decimal place
Display one decimal place
Display two decimal places
Display three decimal places
Display four decimal places
Max. Value
99999
99999
9999.9
999.99
99.999
9.9999
[Figure 3-5 Connecting the Transmitter to HHT]
Figure 3-4 Transmitter Zero/Span Configuration Buttons
P-3100:TEMPLATE 3/1/10 11:28 AM Page 10