Mendota MEDALLION Installation & Operating Instructions Manual Download Page 14

B - 1   VERTICAL THROUGH-THE-ROOF VENTING 

The maximum vertical run of vent pipe is 35 ft. from the top of the stove.  The stove will support a run of a 
maximum of 35 ft.  Maintain 1 1/2” air space clearances on all sides of vents. 

 

IMPORTANT:  REFER TO DRAWINGS ON PAGES 9 & 10 WHILE FOLLOWING THESE INSTRUCTIONS. 

The SDV40 Stove must be installed by a qualified Mendota approved service person. 

1.  Place the stove in its desired location.  Drop a plum bob from the ceiling to the position of the stove flue exit.  

Mark the location where the vent will penetrate the ceiling.  Drill a small hole at this point.  Next, drop a plum 
bob from the roof to the hole previously drilled in the ceiling.  Mark and drill the spot where the vent will 
penetrate the roof.  Determine if ceiling joists, roof rafters or other framing will obstruct the venting system.  
You may wish to relocate the stove or to offset, to avoid cutting load bearing members. 

2.  Cut and frame a 10" x 10" opening in the ceiling centered on the hole drilled in No. 1.  

3.  To determine the length of the vent pipe required, measure the distance from the stove flue outlet to the ceiling, 

the ceiling thickness, the vertical rise in the attic or second story and allow sufficient vent height above roof line.  
For two story installations, firestops are required at each floor level.  If an offset is needed in the attic, additional 
pipe and elbows will be required. 

4.  Assemble the desired lengths of vent pipe and elbows to reach from the stove flue outlet through the Round 

Ceiling Support Box.  Ensure that all pipe and elbow connections are in their fully twist-lock position. (See Page 
8, 

Twist-Lock Piping

)  Maintain 1 1/2" airspace clearances to combustibles. 

5. 

Cut a 10" x 10" opening in the roof, centered in the small drilled hole placed in the roof in No. 1.  The opening 
should be a sufficient size to meet all clearance requirements.  Continue to assemble lengths of pipe and elbows 
necessary to reach the Ceiling Support Box up through the roof line.  Galvanized pipe and elbows may be 
utilized in the attic, as well as above the roof line.  The galvanized finish is desirable above the roofline due to its 
higher corrosive resistance. 

 

a)  If an offset is necessary, it is important to support the vent pipe every 3 ft. to avoid excessive stress on the elbows 

and possible separation.  Wall straps are available for this purpose. 

b)  Whenever possible, use 45

º

 elbows instead of 90

º

 elbows.  The 45

º

 elbow offers less restriction to the flow of 

flue gases and intake air.  If a 90

º

 elbow is necessary there must be a one foot minimum rise from the 90

º

 elbow to 

the vent cap or to the next offset.  A maximum of two 90

º

elbows are allowed per installation. 

 

6.  Slip the flashing over the pipe sections protruding through the roof.  Secure the base of the flashing to the roof 

with roofing nails and seal flashing to roof.  Ensure the roofing material overlaps the top edge of the flashing.  
Verify you have at least the minimum clearance to combustibles at the roof line. 

7.  Continue to add pipe sections until the pipe and the vent cap meet the minimum building code requirements, as 

outlined in No. 8 on the following page. 

a)  For multi-story vertical installation, a ceiling firestop is required at the second floor and any subsequent floors.  The 

opening should be framed to 10" x 10" inside dimensions as described in step No. 5. 

b)  Any occupied areas above the first floor, including closets and storage spaces, which the vertical vent passes 

through, must be enclosed.  The enclosure may be framed and sheet rocked with standard construction materials, 
however, be sure to maintain minimum allowable clearances between the outside of the vent pipe and the 
combustible surfaces of the enclosure. 

 

 

 

1

Summary of Contents for MEDALLION

Page 1: ...TINGUISH ANY OPEN FLAME 5 IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR S PHONE 6 FOLLOW THE GAS SUPPLIERS INSTRUCTIONS 7 IF GAS SUPPLIER IS UNAVAILABLE CALL YOUR FIRE DEPARTMENT DO NOT STORE OR...

Page 2: ...AL TOTAL WEIGHT 225 LB SAFETY AGA CERTIFIED PILOT GENERATOR MILLIVOLT THERMOCOUPLE SYSTEM ACTIVATED WITH SWITCH OR THERMOSTAT GAS REQUIREMENTS SUPPLY PRESSURE NAT GAS 7 W C 5 W C MIN 11 W C MAX L P GA...

Page 3: ...on repair and any adjustments to logs or burner must be done by a qualified service person The Stove should be inspected before use and at least annually by a professional service person More frequent...

Page 4: ...ant Si aucun code n existe suivez la norme ANSI Z223 1 ou la norme CAN CGA ACNOR B149 _______________________________________________ MINIMUM CLEARANCES FROM COMBUSTIBLE CONSTRUCTION Unit to sidewall...

Page 5: ...urce of supplemental heat Air movement options for maximizing heat circulation which can be considered are through the wall grills or floor grills or the continuous operation of central heating blower...

Page 6: ...MENDOTA MEDALLION MENDOTA DIRECT VENT FREESTANDING GAS STOVE SPECIFICATIONS CLEARANCES Figure 2 Specifications Clearances 5...

Page 7: ...ss window door by releasing the 4 turn latches behind side doors rotate latches counterclock wise and pull outward and carefully sliding glass door forward 4 You are now ready to hook up the gas suppl...

Page 8: ...Vertical clearance to ventilated soffit located above the terminal from the center line of the terminal 18 inches 46 cm minimum K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Cle...

Page 9: ...rate vent system Common vent systems are prohibited Do not recess vent termination into a wall or siding WE STRONGLY RECOMMEND THAT FIXED LENGTH PIPE SECTIONS BE USED IN PLACE OF TELESCOPING SECTIONS...

Page 10: ...Galvanized 36 RIGID VENT STACK PIPE Black 48 RIGID VENT STACK PIPE Galvanized 48 RIGID VENT STACK PIPE Black 11 14 5 8 ADJUSTABLE VENT PIPE Black Only 2 90 ELBOW Galvanized 90 ELBOW Black 3 45 ELBOW G...

Page 11: ...ypes of venting system installations A HORIZONTAL THROUGH THE WALL TERMINATION 1 Minimum rise 2 Elevated rise B VERTICAL THROUGH THE ROOF TERMINATION 1 Through typical roof 2 Through existing chimney...

Page 12: ...pendicular to the wall The height of the opening must be located to meet all local and national building codes and not allow the termination to be easily blocked or obstructed If wall being penetrated...

Page 13: ...system is attached If this is the case you may want to adjust the stove location 2 Locate position where vent pipe will pass through any ceilings and will penetrate the outside wall Since vent pipe s...

Page 14: ...rilled hole placed in the roof in No 1 The opening should be a sufficient size to meet all clearance requirements Continue to assemble lengths of pipe and elbows necessary to reach the Ceiling Support...

Page 15: ...tangular hole for the Support Box Cut the hole 1 8 larger than the Support Box outline Lower the Support Box through the hole in the roof until the bottom of the Support Box protrudes at least 2 inche...

Page 16: ...through the center of the chimney system and center the Adapter on the top of the chimney pipe Drill 4 1 8 diameter holes through the Adapter and into the chimney top Insure that you are in fact drill...

Page 17: ...2 1 3cm 5 8 1 6cm 1 2 1 3cm 40 100 1 2 1 3cm 1 2 1 3cm 3 4 2 0cm 1 2 1 3cm 100 150 3 4 2 0cm 1 2 1 3cm 7 8 2 3cm 5 8 1 6cm 150 200 3 4 2 0cm 1 2 1 3cm 7 8 2 3cm 3 4 2 0cm NOTE Some areas allow copper...

Page 18: ...r s capacity is not sufficient to add the Gas Stove an additional inches to inches regulator must be installed for the Stove EXCEPTION Some codes allow 2 PSI 1 4KPA supplies to enter the residence in...

Page 19: ...t be installed in accordance with instructions and local and national codes LIGHTING CHECK OFF LIST All items on Installation Check Off List see above must be completed If thermostat or remote control...

Page 20: ...s in place cycle the burner again to make sure of prompt ignition of burner that flame runs smoothly around burner and does not lift off burner NOTE Flames may not come through coals until glass is in...

Page 21: ...Log Fire View Figure 9 Log Module 2 0...

Page 22: ...Carefully unpack one piece log assembly and center on log rest between Side Log Tabs Place log assembly over front locating pins 5 Place glowing embers wool sparsely on top coals in front of front lo...

Page 23: ...ER DOES NOT COME ON IMMEDIATELY AFTER SECOND TRY RECHECK COMPLETE INSTALLATION OF LOGS PILOT ETC TO INSURE PROPER PILOT FLAME IMPINGEMENT ON THE THERMOPILE AND PROMPT BURNER IGNITION NEVER TURN BURNER...

Page 24: ...in gas pressure B Carbon dirt or lint Have your gas supplier check for correct gas 7 W C Nat Gas 11 W C LP Gas If flame still needs adjustment see Flame Adjustment below Clean out carbon spider webs...

Page 25: ...ves that are put in gas both natural and propane to make it smell can be harmful to glass and can leave a white film deposit on the glass This deposit can be removed with cleaners such as KEL KEM Poli...

Page 26: ...side 7 18 50 01 00017 Pop Rivet 1 8 x 1 4 Aluminum WARNING Use only authorized parts and materials obtained from Johnson Gas Appliance when replacing defective or damaged glass DO NOT substitute other...

Page 27: ...illivolt generation and assure trouble free burner operation Readings must be taken with a Pilot ONLY operating b Main Burner operating A PILOT ONLY OPERATING Thermostat OFF Minimum Millivolts 325 Usi...

Page 28: ...e pg 20 for location Orifice is removed and installed with a deep well socket and ratchet 2 Install pilot orifice 05 04 00036 014 see pg 28 for location Remove and install pilot hood with 7 16 open en...

Page 29: ...K 45 01 00101 908B STACK 6 RIGID VENT BLACK 45 01 00098 911B 11 14 ADJUSTABLE PIPE 45 01 00148 917B ADJUSTABLE PIPE 17 24 BLACK 45 01 00143 945BG ELBOW 45 DEG SWIVEL BLACK 45 01 00142 945G ELBOW 45 DE...

Page 30: ...Piezo Igniter 65 14 00050 Main Orifice L P Gas 50 35 01 00239 Ember Wool 65 06 00435 Metallic Black Paint Spray Can 05 07 00061 Thermopile 50 06 00065 Door Latch 05 07 00067 Thermocouple 50 06 00064...

Page 31: ...urer s specifications INSTALL PROPER SIZE GAS LINES CHECK FOR GAS LEAKS Per Manual CHECK FOR CORRECT GAS PRESSURE AT MANIFOLD Per Manual a 3 5 Inches Water Column Maximum Nat Gas b 10 5 Inches Water C...

Page 32: ...TAPE SHUT POSTAGE NEEDED JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 3 1...

Page 33: ...NOTES NOTES 3 2...

Page 34: ...MENDOTA EXTENDED LIFETIME PROTECTION AND LIMITED WARRANTY MENDOTA MEDALLION SDV40 DIRECT VENT GAS STOVE 3 3...

Page 35: ...warranted against burn out Mendota has the right to investigate and inspect the exact original stove and entire installation without any alterations or tampering in the event a claim is made to determ...

Page 36: ...Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 WEBSITE www johnsongas com 0405 Part 85 03 00701...

Reviews: