30
CHECKING FOR NORMAL BURNER (S) IGNITION CHARACTERISTICS
Once the conversion to LPG and all the above steps have been completed, light the main burners.
Turn Gas Dial counterclockwise to “ON” then set Thermostat or push Main Burner ON/OFF switch to turn on
burners. Main burner should now light IMMEDIATELY and flame should not “lift” off burner. If there is any delay
in ignition or if flame is “lifting off” burner, turn off burner and carefully check for proper installation of logs/coals,
vent system and proper pilot flame impingement on burner and thermopile. Logs or coals must not block pilot
flame or main burner flame. Vent system must be leak proof.
ATTACHING LPG CONVERSION LABELS AND HIGH ALTITUDE DE-RATION LABEL
Two printed informational labels are included with the LPG Conversion Kit. Attach these two labels to inner sur-
face of the left side controls access door. If you are de-rating this appliance at a high altitude, also attach the
High Altitude De-ration Label, supplied in the Owner’s Manual Packet, to this same surface.
Prior to attaching the labels, fill in all the information that is requested in these labels.
For LP installations from 610-1370 meters (2000-4500 ft.) the orifice sizes (DMS) for natural
gas are #47 Front/#39 rear and for propane gas are #57 front/#54 rear.
GAS LEAK TEST REQUIREMENT:
It is the responsibility of the installer/service person to
assure that each and every gas connection and supply tubing that are a part of this fireplace
are leak proof. The qualified/ certified individual connecting the gas supply line, performing
pressure tests or performing any service to this fireplace is required to perform a THOROUGH
LEAK TEST on ALL gas fittings that are a part of this appliance or the gas supply line connec-
tion using soap-water solution or a calibrated combustible gas detector. Failure to perform
this leak test may lead to a house fire and/or an explosion. Mendota is not responsible for any
damages due to an Installer’s failure to conduct a leak test and verify that all connections and
supply lines are leak proof.
WARNING: Do not operate appliances with glass front removed, cracked, or broken.
Replacement of glass should be done a licensed or qualified service person.
Note: Consult the local or national installation code(s) to assure that adequate combus-
tion and ventilation air is available.