MENDOTA WARRANTY QUALIFICATION & SERVICE REFERENCE FORM
As a part of Mendota's on-going program of customer satisfaction, this Form verifies proper installation and operation. It is im-
portant as a reference for future service. It insures long life and trouble-free operation of Mendota fireplaces & stoves and quali-
fies the owner for Mendota's lifetime limited warranty. Owner should sign Form when completed and mail a copy along with
Warranty Registration to Mendota. OPTIONALLY, PLEASE REGISTER AT OUR WEBSITE AT:
WWW.JOHNSONGAS.COM/MENDOTA-REGISTRATION.ASP
HOME OWNER: ________________________________
DEALER: _________________________________
ADDRESS: ____________________________________
ADDRESS: _______________________________
CITY/STATE/ZIP: ______________________________
CITY/STATE/ZIP: __________________________
SIGNATURE: __________________________________
PHONE: __________________________________
MODEL #: FV41-M SERIAL #: _____________
DATE INSTALLED: ________________________
Mendota direct vent fireplaces are sophisticated, hi-tech gas appliances. All installation and operating instructions must be carefully
followed. This FV41-M fireplace must be installed and serviced by a qualified Mendota approved service person.
REF: ___________________ MENDOTA FV41-M INSTALLATION MANUAL
APPROVED VENT PIPES AND VENT CAP INSTALLED - Per Manual.
Vent pipes must be fully twist-locked and leak proof.
Check minimum and maximum vertical / horizontal and vent runs.
1000
º
sealant must be used on inner joints at adjustable pipe sections
.
CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES & VENT LOCATIONS - Per Manual
INSTALL PROPER SIZE GAS LINES - CHECK FOR GAS LEAKS - Per Manual
CHECK FOR CORRECT GAS PRESSURE AT MANIFOLD - Per Manual
a.
3.5 Inches Water Column Maximum - Nat. Gas
b.
10.0 Inches Water Column Maximum - L.P. Gas
CYCLE BURNERS ON/OFF FOR PROMPT IGNITION - Per "LIGHTING INSTRUCTIONS"
Burner must light IMMEDIATELY - Flame must travel promptly around "curve" & light burner
.
INSTALL LOGS AND ADJUST FLAME - Per Manual
Proper pilot flame impingement on Flame Sensor & burner - Air shutter opening: 1/8" Nat. Gas – 5/16"-1/2" LP
Check that flame is "stable" and is not "lifting" off burner
BRIEF OWNER ON OPERATION AND MAINTENANCE OF UNIT
Light Pilot
Operate Burner
Train on Remote Control Functions
Explain Thermostatic Functions
WARRANTY REGISTRATION
Your Name _______________________________________________________________________
Address _________________________________________________________________________
City ________________________________________ State ______Zip ______________________
Dealer (Place of Purchase) ___________________________________________________________
City ________________________________________ State ______Zip ______________________
Date of Purchase _______________________ Serial Number _______________________________
Purchaser's Signature _______________________________________________________________
MENDOTA FV41-M DIRECT VENT FIREPLACE
CUT OUT PAGE AND MAIL TO: JOHNSON GAS APPLIANCE CO., 520 E AVE. N.W., CEDAR RAPIDS, IOWA 52405
PLEASE REGISTER AT OUR WEBSITE AT: WWW.JOHNSONGAS.COM/MENDOTA-REGISTRATION.ASP