Mendota DXV-35 DEEP TIMBER II Installation & Operating Instructions Manual Download Page 17

 16 

A-1 

MINIMUM RISE THROUGH-THE-WALL VENTING

 

The minimum vertical rise for vent installation through the wall is 16 1/4" from the top of the fireplace to the 
centerline of the 90

º

 elbow in installations where only a 6” (or 7”) horizontal vent section is used (refer to chart 

on pg.14 when using horizontal sections).  NOTE:  We recommend always using the most vertical rise the in-
stallation will allow.  This maximizes efficiency and flame appearance.  This is especially true for LP gas instal-
lations and for installations at higher altitudes.  Use "fixed" pipe sections in place of adjustable pipe sections 
wherever possible.  1000

º

 sealant must be used on ALL inner pipe joints.  Always maintain 1" clearances from 

vent pipe to combustibles, 2" above pipe on horizontal runs.   Do not fill air spaces with insulation or other ma-
terial.   

For 

L.P. gas and High Altitude (above 4,000 ft.),

 45

º

 elbows must be used in place of 90

º

 elbows.   

NOTE:  This requires 19" minimum rough opening depth (see pg. 15 CAUTION:  If 90

º

 elbows must be used, 

a 3-foot vertical starter section must be used directly off the top of the fireplace. 

The DXV-35 Fireplace must be installed by a qualified Mendota approved service person. 

1.

 

Position fireplace in desired location.  See pg. 8 for guidelines on proper vent cap placement on the exterior 
of home.  Check to determine if wall studs are in the way when venting system is attached.  If this is the 
case, you may want to adjust the fireplace location. 

2.

 

Measure from the top of the fireplace up minimum (see Figure 4: Specifications & Clearances, pg. 12) and 
mark wall directly at the center of where the vent pipe will penetrate the wall. 

3.

 

Cut and frame a 9" wide x 10" high opening in the wall.  The hole must be positioned so the vent system 
will run level or have a ¼" rise AND be perpendicular to the wall.  The height of the opening must be locat-
ed to meet all local and national building codes and not allow the termination to be easily blocked or ob-
structed.  If wall being penetrated is non-combustible material, i.e. masonry block, brick, etc., a 7-inch 
diameter hole is acceptable. 

4.

 

Assemble the components to the fireplace adapter with pipe seams oriented toward the wall or floor -- as 
much out of view as possible.  Be sure all vent component connections are in their fully twist-locked posi-
tion and are leak-proof.  Be sure 1000

º

sealant is used on the inner pipe joints of all pipe sections manufac-

tured by Simpson DuraVent.  American Metal pipe joints do not required this sealant. 

5.

 

The length of the horizontal piece that fits through the wall will be determined by the thickness of the wall.  
When installed, the end of the horizontal piece must be flush with the exterior wall of the home.  There 
MUST be a minimum of 1" air space clearance to combustibles from all vent pieces (2" above horizontal 
runs). 

6.

 

A wall thimble must always be used when penetrating combustible wall materials. 

NOTE:  Combustible wall thickness must be 4" to 8" maximum. 

7.

 

From the exterior of the home, slide the horizontal vent cap over the end of the horizontal pipe and tightly 
secure the cap to the wall with screws.  Seal with a high quality caulking. 
NOTE:  Venting terminal should not be recessed into wall or siding. 

 
 

IMPORTANT:  REFER TO DRAWINGS ON PAGES1215 WHILE FOLLOWING THESE INSTRUCTIONS

 

NOTE: DO NOT SEPARATE TELESCOPING SECTIONS. 

 

THEY MUST BE USED AS COMPLETE  ASSEMBLIES. 

Summary of Contents for DXV-35 DEEP TIMBER II

Page 1: ...4 EXTINGUISH ANY OPEN FLAME 5 DO NOT USE THE PHONE IN YOUR BUILDING 6 IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR S PHONE 7 FOLLOW THE GAS SUPPLIERS INSTRUCTIONS 8 IF YOU CANNOT REACH YOUR GAS...

Page 2: ...________________________________________________________________19 RANDOM LOG INSTALLATION ____________________________________________________________________________22 TIMBERFIRE LOG SET INSTALLATI...

Page 3: ...sting and certification agency to American National Standards Institute ANSI Gas Appliance Safety Standards The Mendota Gas DXV Fireplace has been tested and certified by Intertek Testing Services 843...

Page 4: ...stallation repair and any adjustments to logs or burner must be done by a qualified service person The Fireplace should be inspected before use and at least annually by a professional service person M...

Page 5: ...earances pg 12 and pg 22 Non combustible marble brick stone etc mantels or mantels with steel protector plate on underside can be installed at any desired height above upper grill Never block off uppe...

Page 6: ...t Pipes AMERIVENT DURAVENT SELKIRK METALBESTOS SECURITY CHIMNEY brand pipes and venting components may be used when venting off the top Venting off the top on the DXV 35 Fireplace provides a large deg...

Page 7: ...ff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 PSIG 3 5 kPa The proper gas line diameter must be selected to run from the supply regul...

Page 8: ...place an additional inches to inches regulator must be installed for the Fireplace EXCEPTION Some codes allow 2 PSI 1 4KPA supplies to enter the residence in which case pounds to inches regulators are...

Page 9: ...ffit located above the terminal from the center line of the terminal 18 inches 46 cm minimum Vinyl surfaces require 24 min K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Clearance...

Page 10: ...nce Mendota Direct Vent Fireplaces and Stoves it is critical that the DuraVent GS and American Metals vent pipe sections are sealed tightly and leak proof This means that all pipe sections must be car...

Page 11: ...ials may overlay nailing flanges and come in contact with the edges of the black front surface but may not overlay the 2 black front sur face Noncombustible material such as marble or brick can be ins...

Page 12: ...ace Failure to follow all directions and failure to observe all restrictions and clearances can result in property damage bodily injury or can lead to death TOP VENTING REQUIRES AMERIVENT DURAVENT SEL...

Page 13: ...45 angle to the front face and starting at the side edge of this appliance is allowed Projections behind this 45 angle edge shaded area are allowed R 1 RATED HEARTH PAD REQUIRED USE R 1 RATED BOARD A...

Page 14: ...9 ATTIC INSULATION SHIELD 12 10 ROOF FLASHING 0 12 TO 6 12 10 ROOF FLASHING 7 12 TO 12 12 11 STORM COLLAR 12 VERTICAL VENT CAP 13 SUPPORT BAND 14 HORIZONTAL VENT CAP 15 FIRESTOP SPACER If adjustable...

Page 15: ...MS NOTE FOR LP GAS HIGH ALTITUDE SEE PG 15 NOTE 9 MINIMUM RISE CAN BE USED IF NO HORIZONTAL VENT SECTIONS GREATER THAN 6 or 7 ARE USED ALL OTHER INSTALLATIONS MUST FALL WITHIN ABOVE SHADED AREA Figure...

Page 16: ...45 COAX VENT 15 1 2 85 03 00531 For L P gas and high altitude installations above 4 000 ft 45 elbows must be used in place of 90 elbows NOTE This requires 19 minimum height to center CAUTION If 90 elb...

Page 17: ...e center of where the vent pipe will penetrate the wall 3 Cut and frame a 9 wide x 10 high opening in the wall The hole must be positioned so the vent system will run level or have a rise AND be perpe...

Page 18: ...2 PITCH 45 01 00202 FLASHING 6 12 12 12 PITCH 45 01 00203 STORM COLLAR 45 01 00204 ATTIC INSULATION SHIELD 45 01 00206 CO LINEAR APPLIANCE ADAPTOR 45 01 00207 CO LINEAR TOP KIT 45 01 00208 VERTICAL KI...

Page 19: ...netrate the outside wall Since vent pipe sections overlap we suggest pre assembling and measuring the total vent pipe run so you can more accurately locate the point where the vent pipe will penetrate...

Page 20: ...f in No 1 The opening should be a sufficient size to meet all clearance requirements Continue to assemble lengths of pipe and elbows necessary to reach up through the roof line Galvanized pipe and elb...

Page 21: ...ent cap can be determined as follows H DIMENSION ROOF PITCH FEET METERS FLAT to 6 12 2 6 7 12 to 9 12 2 6 10 12 to 12 12 4 1 2 13 12 to 16 12 6 1 8 17 12 to 21 12 8 2 4 8 Complete installation with st...

Page 22: ...frame 2 Pull Glass Latch Tool outward about 3 8 3 Rotate Glass Latch Tool 90 degrees 4 Slowly Release Glass Latch Tool 5 Remove Glass Latch Tool To Latch Glass Frame Latches reverse steps 5 to 1 above...

Page 23: ...front surfaces of log for additional glow Add wool to burned out space between front logs Fill area to back burner WARNING Do not block holes with excessive wool Delayed ignition and sooting can occu...

Page 24: ...23...

Page 25: ...24...

Page 26: ...25...

Page 27: ...26 The following Check Off Lists must be completed prior to final operation of the Fireplace or manufacturer s warranty and liabilities will be voided...

Page 28: ...leted Connect thermostat to gas valve terminals TPTH TH Use solid copper wire See page 40 for wires specifications System Millivolt readings must be taken by a qualified installer CAUTION Pilot flame...

Page 29: ...2 hrs 9 Reinstall glass front screen by hanging slots on upper edge of door over tabs on upper edge of firebox opening Then swing in lower edge of door Carefully pull out the two 2 Spring Loaded Door...

Page 30: ...in button firmly until unit lights DO NOT push button and release quickly before burner lights Burner should light IMMEDIATELY and then button can be released If unit does not light imme diately relea...

Page 31: ...eration after servicing BLOWER OPERATION The Mendota DXV Fireplace is designed so the blower operates at all times the fireplace is operating The blower output can be regulated with the rheostat inclu...

Page 32: ...e Flame Adjustment below Clean out carbon spider webs lint etc from shutter area Logs and burner NEVER BLOCK AIR INTAKE OR OUTLET VENTS Figure 9 Air Shutter GAS FLAME ADJUSTMENT Be sure burner and log...

Page 33: ...xterior glass may be cleaned with cleaner as desired Inte rior glass use soap and water CAUTION Do Not use oven cleaner to clean glass NOTE Additives that are put in gas both natural and propane to ma...

Page 34: ...LATION check off lists are completed see pg 39 2 COMBUSTION SYSTEM MILLIVOLT READING Millivolt readings must be taken by a qualified installer at the time of installation and after any interruption in...

Page 35: ...esired Interior glass use KEL KEM Polish Plus part 65 06 00455 or comparable product Do Not use oven cleaner or abrasive cleaners to clean glass DO NOT CLEAN WHEN GLASS IS HOT 4 PERIODIC VISUAL CHECK...

Page 36: ...t 2 Install pilot orifice 05 04 00036 014 see pg 45 for location Remove and install pilot hood with 7 16 open end wrench Pilot orifice thimble is located inside pilot hood base 3 Install the new LP Pr...

Page 37: ...AT 35 01 00275 FIREBRICK KIT 15 02 00062 BLOWER ASS Y HA 30 00230 VALVE ASS Y SIT 15 02 00064 R H BLOWER WITH MOTOR 05 02 00306 VALVE NAT GAS 15 02 00065 L H BLOWER WITH MOTOR 05 01 00157 THERMO DISC...

Page 38: ...in the diagram below Any material that protrudes into this area on the sides top or bottom edges can only be flush with the front surface of the fireplace faceplate If planning to install either the...

Page 39: ...The top and sides of these trim kits fit with in the inner perimeter of the Fireplace s Faceplate The bottom member of this trim however overlaps the bottom 2 black boarder of the fireplace front face...

Page 40: ...re low in w c 1 7 3 6 Minimum Inlet Pressure in w c 5 0 11 0 _______________________________________________ This appliance is equipped for installation at 0 610 meters This appliance must be installe...

Page 41: ...ARANCES TO COMBUSTIBLES VENT LOCATIONS Per Manual INSTALL PROPER SIZE GAS LINES CHECK FOR GAS LEAKS Per Manual CHECK FOR CORRECT GAS PRESSURE AT MANIFOLD Per Manual a 3 5 Inches Water Column Maximum N...

Page 42: ...41 TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Page 43: ...erformance of any part of this limited warranty Mendota has the right to investigate and inspect the exact original Fireplace and entire installation without any alterations or tampering in the event...

Page 44: ...Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division WEBPAGE www johnsongas com or www mendotahearth com Part 85 03 00686...

Reviews: