MAINTENANCE INFORMATION
6.1
REQUIRED PERIODIC INSPECTIONS
1.
Check to verify that the vent system and vent cap are open and free of blockage.
2.
Have qualified service person check the operation of the pilot light. Pilot light must light within the first five to eight
seconds of ignitor sparks initiation. If it takes more ten seconds to ignite the pilot flame, check pilot spark rod position and
ignitor wires for pinched areas or damaged areas.
3.
Periodic visual check of pilot flames is required. Pilot Flame must overlap thermocouple tip and burner ignition ports
always. Especially for LPG applications, always verify visible
pilot flame length is at least 1" long, minimum.
4.
Cycle the burners to make certain burner ignition is prompt
and flame propagation along burner length is quick and
smooth. If flame propagation is delayed, remove obstructing
debris, vacuum burner ports and retry.
5.
Periodic visual check of rear and front burner flames pattern
is required.
6.2
CLEANING VIEWING GLASS
WARNING: Do not clean when glass is hot.
The viewing glass should be cleaned periodically. Exterior glass
surface may be cleaned with cleaner as desired. To clean Interior
glass surface, remove glass frame assembly.
Use Kel Kem “polish
plus" (part # 65-06-00455) or comparable product to clean glass
interior surface. Do not use oven cleaner or abrasive cleaners to
clean glass.
floor is more than ¼” out of level from one side to another or from front to back. If the
less than ¼” out of level, use metal sheet shims in various thickness and bu
ild up to needed leveling thicknesses at various points
SUCH NOISE PROBLEMS ARE NOT COVERED UNDER MENDOTA
actory bricks to build up a full level
Figure 6-1 Pilot Flame Lengths