Gas Input Rate Verification
Natural Gas Input Rate Verification
1. Verify main orifice size. The main orifice body has the orifice hole size stamped on it. NG orifice size shall be #32 for
all elevations.
2. Verify that the Manifold Gas Pressure is within 3.5" WC +/- 1/8".
Once setup, read the main home gas supply meter reading.
3. Write the initial reading here >> initial gas meter reading
Turn off all other appliances and their pilot flame in the home.
4. Run this appliance for a period of 30 minutes on maximum flame size. Turn off main burner and pilot
flame. Read the main home gas supply meter reading after the 30 minutes of burn time.
5. Write the reading here >> final gas meter reading
Calculate the following:
6. FINAL GAS METER READING - INITIAL GAS METER READING...Subtract initial gas meter from final gas meter
reading. This will yield the number of Therms used during the 30-minute burn time.
7. Multiply the result in Item #6 by 100,000.
8. Multiply the result in Item #7 by 2. Write down the result here >>
9. The result in item #8 shall be at least the maximum input rate (34,000 Btu/hr.) for all altitudes.
LPG Input Rate Verification
Verify main orifice size. The main orifice body has the orifice hole size stamped on it. LPG orifice size shall be #50 for all
elevations.
Verify that the manifold gas pressure is within 10.0" WC +/- 1/8".
High Altitude De-Rating
This fireplace does not need to be de-rated for high altitude use. See data plate for additional information. For high
altitude installations consult the local gas distributor or the authority having jurisdiction for proper rating methods.