Mendip SOMERTON 2 Pedestal Operation And Installation Manual Download Page 4

4

The  outlet  from  the  chimney  should  be  above  the  roof  of  the  building  in  accordance  with  the  provisions  of  Building

Regulations Approved Document J. If installation is into an existing chimney then it must be sound and have no cracks or
other faults which might allow fumes into the house. Older properties, especially, may have chimney faults or the cross
section may be too large i.e., more than 160 mm x 160 mm.

Mendip Stoves recommend the use of a solid fuel flue lining system for all installation into existing chimneys. All chimney
systems must be used in accordance with Building Regulations Approved Document J.

If an existing chimney  is used the  chimney must be clear of obstruction and  be swept clean immediately before installation
of the stove. The chimney should be tested to confirm the chimney will provide the correct chimney pressure for the stove.
If the stove is fitted in place of an open fire  the chimney should be swept one month after installation to clear any soot falls
which may have occurred due to the difference in combustion between the stove and the open fire. If there is no existing
chimney then either a prefabricated block chimney in accordance with Building Regulations Approved Document J or a twin
walled insulated stainless steel flue to BS 1856-1 . These chimneys must be fitted in accordance with the manufacturer’s
instructions and Building Regulations. A single wall metal flue pipe is suitable for connecting the stove to the chimney but
is not suitable for using for the complete chimney. The chimney and connecting flue pipe must have a minimum diameter
of 150 mm and its dimension should be not less than the size of the outlet socket of the stove. Any bend in the chimney or
connecting flue pipe should not exceed 45

°

.  90

° 

bends should not be used other than  within 150 mm of stove rear flue

outlet.

Chimney Connection

In order for the stove to perform satisfactorily the chimney height must be sufficient to ensure an adequate

draught to clear the products of combustion and prevent smoke problems into the room.

Tested Gas flow rates flue
gas temperatures

Flue gas flow rate

Wood

Test flue gas temperature

Wood

@ pascals of pressure

Somerton 2 SG

7.9g/sec 

289 °C 

12 Pa.

FLUE & CHIMNEY CONNECTION TO STOVE

A chimney height of not less than 4.5 metres measured vertically from the outlet of the stove to the top of the chimney

should be satisfactory. Alternatively the calculation procedure given in BS5854:1980 may be used as the basis for deciding
whether a particular chimney design will provide sufficient draught.

If it is found that there is excessive draught in the chimney then either an adjustable flue damper or alternately a draught
stabiliser should be fitted. The adjustable flue damper should not close off the flue entirely but should in its closed position
leave a minimum continuous opening free area of at least 20 % of the total cross sectional area of the flue or flue pipe.

Adequate provision e.g. easily accessible soot door or doors must be provided for sweeping the chimney and connecting flue

pipe.

Your appliance needs to be maintained routinely, the throat plate/baffle should be cleaned regularly (monthly) . The flue

pipe can be cleaned using a flexible brush. Only Use a dry cloth on external surfaces. Over time the glass may become dirty,
clean with a damp cloth and polish off with damp cloth.  If the stove has not been used for some time  the flue should be
checked for blockages before use. Do not modify the appliance; only use spares authorised by the manufacturer.

Summary of Contents for SOMERTON 2 Pedestal

Page 1: ...1 Operation and Installation Manual SOMERTON 2 Side Glass WOOD STOVE Manuel de l Utilisateur et Mode d Emploi ENG FR Somerton 2 SG FEB 2016...

Page 2: ...any potential operational problems Please note that all local regulations including those referring to national and European Standards need to be complied with when installing this appliance For furth...

Page 3: ...in the same room as the appliance Further guidance on the installation of the carbon monoxide alarm is available in BS EN 50292 2002 and from the alarm manufacturer s instructions Provision of an alar...

Page 4: ...e outlet socket of the stove Any bend in the chimney or connecting flue pipe should not exceed 45 90 bends should not be used other than within 150 mm of stove rear flue outlet Chimney Connection In o...

Page 5: ...tible materials should not be located where the heat dissipating through the walls of fireplaces or flues could ignite it Therefore when installing the stove in the presence of combustible materials d...

Page 6: ...6 Stove dimensions and connection measurements 420mm 985mm 495mm 460mm 150mm 1100m 135mm 130mm 100mm...

Page 7: ...ioning the stove in a corner position with combustible walls the stove must be 150mm at the corners points to achieve 500mm from the side glass to the side wall If the walls are non combustible the co...

Page 8: ...prefabricated factory made insulated metal chimney Hearth Combustion chambers Commissioning and handover Ensure loose parts brick and grates are fitted in accordance with the instructions given in the...

Page 9: ...ing your stove for first time make sure you have read this manual fully and acquainted yourself with the controls of this appliance see page 9 The heat resistant paint on your stove will cure and hard...

Page 10: ...educes and out increases the total amount of combustion air in the stove Moving the control lever from left to right By moving the control lever to the left increases the primary air mix and moving to...

Page 11: ...tove flames begin to falter and generate smoke in chamber unlatch the door again until the fire is established 6 Once the fire bed is established slide UAC control to the secondary position and push i...

Page 12: ...rol areas see page 5 alterations should not be attempted Mendip smoke control stoves should not be burnt with the door left open The refuelling procedure allow the newly charged fuel to burn with the...

Page 13: ...the new wood has taken and is burning then close the secondary air valve to its operational position On returning to the stove in the morning the fire will have burn out reload with some paper or fir...

Page 14: ...14 Somerton combustion chamber Secondary air air wash Tertiary Air bar Vermiculite brick set Cast iron grate Log retainer wing Ash pan with seal Firebrick Baffle Double glazed side glass...

Page 15: ...nd pull out of firebox chamber Take care to support ash pan during movement always wear a heat resistant glove Make sure the stove is completely cold before cleaning out ash embers can remain hot for...

Page 16: ...SIDES M90700 01 15 99 01 SOMERTON GLASS CLAMPS BOTTOM TOP M90700 06 02 01 01 DOOR ROPE SEAL M90700 01 02 01 01 GLASS ROPE SEAL 5 6 6 2 3 1 4 7 M90703 02 05 99 00 M90703 02 04 99 00 M90703 02 18 99 00...

Page 17: ...3 20 09 00 00 M10703 01 21 99 00 M90700 18 00 00 01 M10703 01 21 99 00 M90800 11 07 99 00 M90703 15 07 00 00 M90700 20 05 99 00 M90700 11 10 30 01 M90700 06 00 00 01 M90703 20 08 00 00 M10703 01 20 99...

Page 18: ...SOMERTON SIDE GLASS DOOR CONSTRUCTION SOMERTON SIDE GLASS BASE FRAME DOOR CONSTRUCTION...

Page 19: ...Mendipstoves co uk E mail info mendipstoves co uk Distribu en France par la soci t Distributed in France and Benelux by Eurostove SAS Centre d Affaires Rue de L horlogerie BP 60011 62401 Bethune Cede...

Reviews: