MINIMUM DISTANCE TO NON-COMBUSTIBLE MATERIALS

The stove can be recessed in a suitable sized non - combus�ble fireplace but a

permanent free air gap of at

least 50mm

must be le� around the sides, the top and the back of the stove; this is to facilitate a reasonable

heat output and allows access to the stove for removal and maintenance.

A clearance of 100mm will give a be�er heat output.

All non - combus�ble walls closer than 100mm to the stove should be at least 75mm thick. For prac�cal reasons
the back wall of the fireplace recess and the hearth should ideally be made of non -combus�ble material. When
installing your stove in a non combus�ble chamber, combus�ble materials should not be located where the
heat dissipa�ng through the walls of fireplaces or flues could ignite it. Therefore when installing the stove in
the presence of combus�ble materials due account must be taken of the guidance on the separa�on of
combus�ble material given in Building Regula�ons Approved Document J and also in these stove instruc�ons.
The minimum distances to flammable materials are specified on the EN 13240 plate on the back of the stove.

HEARTH

The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not
independently supported. The Woodland DS stove has been tested and is suitable to be installed on a 12 mm
non combus�ble plate, such as 12 mm glass plates . Installa�on of all hearths should comply in size and
construc�on so that it is in accordance with the provisions of the current Building Regula�ons Approved
Document J.
The clearance distances to combus�ble material beneath, surrounding or on the hearth and walls adjacent to
the hearth should comply with the guidance on the separa�on of combus�ble material given in Building
Regula�ons Approved Document J and also in these stove instruc�ons.
If the stove is to be installed on a combus�ble (wooden) floor, it must be covered with a non-combus�ble material
at least

12 mm thick

, in accordance with Building Regula�ons Approved Document J, to a distance of

30 cm in

front of the stove

and

15 cm to each side

measuring from the door of the combus�on chamber.

Summary of Contents for WOODLAND DS

Page 1: ...installa on et Mode d emploi MODELES D EXEMPTION POUR LA COMBUSTION DU BOIS WOODLAND DOUBLE FACE WOODLAND DOUBLE FACE RANGE B CHE MODELE PIEDESTAL The Woodland Double sided Catalyst M00730 00 00 00 0...

Page 2: ...325mm FLUE OUTLET DIAMETER Diam tre du conduit de fum e D 125 mm 125 mm CENTRE OF FLUE TO FRONT OF STOVE Centre du conduit de fum e l avant du po le E 215mm 215mm CENTRE OF AIR INTAKE TO FRONT OF BODY...

Page 3: ...rostove on your behalf Register online today to ac vate warranty online h p www mendipstoves co uk SIT stoveregistra on INSTALLATION MANUAL This manual refers to the Woodland Double sided which is tes...

Page 4: ...noxide alarm must be fi ed in the same room as the appliance Further guidance on the installa on of the carbon monoxide alarm is available in BS EN 50292 2002 and from the alarm manufacturer s instruc...

Page 5: ...top plate allowing enough room to drill a hole through the flue collar and into the flue pipe 3 Secure the collar and flue pipe with a suitably sized self tapping screw Woodland DS Catalyst Converter...

Page 6: ...ke exempt models with a 125mm collar burning wood only can be installed on a flue of 125mm throughout Any bend in the chimney or connec ng flue pipe should not exceed 45 90 bends should not be used ot...

Page 7: ...uilding Notes 1 The weather surface is the building external surface such as its roof les or external walls 2 A flat roof has a pitch less than 10 3 The clearances given for A or B as appropriate will...

Page 8: ...9 0 08 W 20 116 109 YES Tested Gas flow rates flue gas temperatures Flue gas flow rate Wood Test Flue gas Temperature wood coal Pascals Pressure Woodland DS 7 2 g sec 310 Deg C 12pa Log Length Wood R...

Page 9: ...proved Document J and also in these stove instruc ons The minimum distances to flammable materials are specified on the EN 13240 plate on the back of the stove HEARTH The hearth should be able to acco...

Page 10: ...boltsat thefoot of the stove leg Posi on the Log store legs and use the levelling feet to secure them to the body of the stove Use a spanner or a socket wrench to fully Tighten Right the stove and se...

Page 11: ...e rear of the stove TheaircontrolontheWoodlandDSModel has 40mmtravelontheaircontrol TheSEfixingisdesigned to prevent the air supply of the stove from being completely shut off this promotes complete c...

Page 12: ...with preserva ves or any house hold waste DO NOT EXCEED SPECIFIED FUEL WEIGHTS DO NOT BURN HOUSE COAL DO NOT BURN HOUSEHOLD WASTE THIS APPLIANCE IS NOT AN INCINERATOR LIGHTING YOUR STOVE FOR THE FIRS...

Page 13: ...low the stove door so that it is to the le and fully open pulled out this provides the stove with a mix of primary and secondary air to help establish the fire 3 Light the firelighters and push door t...

Page 14: ...isters Further informa on on the requirements of the Clean Air Act can be found here h ps www gov uk smoke control area rules Your local authority is responsible for implemen ng the Clean Air Act 1993...

Page 15: ...e stove requiresa permanent airvent to theroom Thisis to provideadequate air supplyin order for the stove to operate safely and efficiently In accordance with current Building Regula ons the installer...

Page 16: ...being used e the door seals are in good condi on F the chimney draw may be too strong G check ash pan seal and H check for ash below ash pan causing pan to seat incorrectly and clean out 3 Soot forms...

Page 17: ...rned fuel residues To enable a good flow of air through the appliance to reduce condensa on and subsequent damage leave the air controls fully open It is important that the flue connec on any applianc...

Page 18: ...hange LOOSE PARTS PI CES D TACH ES Always use the opera ng tools provided when handling parts likely to be hot when the stove is in use Your stove has the following parts in the stove 1 Cast Iron grat...

Page 19: ...The baffle bricks will now come out easily Enlever les chicanes en re rant 8 ges d acier des parois lat rales Les d flecteurs s enl veront alors facilement 3 Remove side bricks Enlevez les briques la...

Page 20: ...these parts please visit www eurostove co uk the woodland furnace door Woodland Double sided Handle assembly VUE ECLATEE DE LA PORTE Pourplusde d tails ainsiquepourobtenirdesprixetla disponibilit dec...

Page 21: ...21 of 40 1 2 2 25 1 316 477 25 316 340 8 1 1 1 Woodland Double sided Vermiculite Brick set Woodland Double face set de d flecteurs en Vermiculite...

Page 22: ...22 of 40 Defra air control stop for smoke control areas Arr t du contr le de l air pour les zones de contr le des fum es...

Page 23: ...z qui l appareil a t achet qui vous offrira une assistance imm diate ou contactera Eurostove en votre nom Inscrivez vous d s aujourd hui pour activer la garantie en ligne http www mendipstoves co uk S...

Page 24: ...ou de remplacement est install dans un logement un d tecteur de monoxyde de carbone doit tre install dans la m me pi ce que l appareil Des conseils suppl mentaires sur l installation du d tecteur de...

Page 25: ...sant suffisamment d espace pour percer un trou dans la buse et le buselot 3 Fixez la buse et le buselot avec une vis auto perceuse de taille appropri Convertisseur catalytique Woodland DS Le po le dou...

Page 26: ...exempts de fum e avec un collier de 125mm br lant uniquement du bois peuvent tre install s sur un conduit de 125 mm de diam tre Tout coude de la chemin e ou du tuyau de raccordement ne doit pas d pas...

Page 27: ...Point de passage des fum es surface m t o Note 1 2 Distances sor e chemin e A A 600mm ou moins de la Au moins 600mm au dessus de corniche la corniche Au moins 2300mm horizontalement du point le plus p...

Page 28: ...r des d bits et des temp ratures d mission D bit des gaz de combustion bois Temp Des gaz de combustion du bois charbon Pression Pa Woodland DS 7 2 g sec 310 Deg C 12pa Puissanc e kW CO 13 Par cules 13...

Page 29: ...donn s dans le r glement de construc on et dans les pr sentes instruc ons rela ves au po le Les distances minimales par rapport aux mat riaux inflammables sont sp cifi es sur la plaque EN 13240 l arr...

Page 30: ...niveau au pied du po le Posi onnez les pieds du Range b che et u lisez les pieds de positionnement pour les fixer au corps du po le U lisez une cl mole e ou une cl douille pour les serrer fond Redres...

Page 31: ...de l exon ra on des fum es Les mod les sans fum e SE sont quip s en usine d un arr t d air sur la glissi re de contr le de l air Pour r gler les param tres de contr le de la fum e u lisez une cl Alle...

Page 32: ...les combustibles recommand s pour le po le Conseillez l u lisateur sur ce qu il doit faire en cas d mission de fum e ou d mana ons du po le Le client doit tre invit u liser un pare feu conforme aux r...

Page 33: ...de bonne qualit est le facteur le plus important pour que votre po le fonctionne efficacement et proprement Utilisez toujours du bois de chauffage fendu sec teneur en humidit de 20 ou moins La s cher...

Page 34: ...et vos b ches comme indiqu 2 Posi onnez le levier du contr le universel de l air UAC sous laportedupo ledemani re cequ ilsoit gaucheetcompl tement ouvert r cela fournit au po le un m lange d air prima...

Page 35: ...de ma re en combus on dans le foyer pour allumer une nouvelle charge de combustible il peut se produire une mission excessive de fum e Le ravitaillement doit tre effectu sur une quan t suffisante de b...

Page 36: ...bouche d a ra on ne doit en aucun cas tre ferm e ou scell e ATTENTION Correctement install u lis et entretenu ce po le n mettra pas de fum es dans la maison Des fum es occasionnelles peuvent se d gage...

Page 37: ...en bon tat F Que le rage de la chemin e ne soit pas trop fort G Le joint du bac cendres et H La pr sence de cendres sous le cendrier ce qui entra ne un mauvais positionnement du cendrier et son ne oya...

Page 38: ...t les r sidus de combus ble non br l s Pour perme re une bonne circula on de l air dans l appareil afin de r duire la condensa on et les dommages qui en d coulent laissez les commandes d air en rement...

Page 39: ...39 of 40 A A B C D E F G 2015 1186 kW ENERGIA ENERGIJA ENERGY ENERGIE A A A Mendip Stoves Ltd Woodland Double Sided 8 0 MP WOODLAND DOUBLE SIDED ENERGY LABEL M10730 49 02 99 00 VERSION 1 0 SEPT 2019...

Page 40: ...Industrial Estate Mendip Road Rooksbridge Somerset BS26 2UG Website www mendipstoves co uk Email info eurostove co uk Telephone 01934 750 500 Part of the Eurostove Group Woodland Double sided Manual...

Reviews: