MINIMUM DISTANCE TO NON-COMBUSTIBLE MATERIALS
The stove can be recessed in a suitable sized non - combus�ble fireplace but a
permanent free air gap of at
least 50mm
must be le� around the sides, the top and the back of the stove; this is to facilitate a reasonable
heat output and allows access to the stove for removal and maintenance.
A clearance of 100mm will give a be�er heat output.
All non - combus�ble walls closer than 100mm to the stove should be at least 75mm thick. For prac�cal reasons
the back wall of the fireplace recess and the hearth should ideally be made of non -combus�ble material. When
installing your stove in a non combus�ble chamber, combus�ble materials should not be located where the
heat dissipa�ng through the walls of fireplaces or flues could ignite it. Therefore when installing the stove in
the presence of combus�ble materials due account must be taken of the guidance on the separa�on of
combus�ble material given in Building Regula�ons Approved Document J and also in these stove instruc�ons.
The minimum distances to flammable materials are specified on the EN 13240 plate on the back of the stove.
HEARTH
The hearth should be able to accommodate the weight of the stove and its chimney if the chimney is not
independently supported. The Woodland DS stove has been tested and is suitable to be installed on a 12 mm
non combus�ble plate, such as 12 mm glass plates . Installa�on of all hearths should comply in size and
construc�on so that it is in accordance with the provisions of the current Building Regula�ons Approved
Document J.
The clearance distances to combus�ble material beneath, surrounding or on the hearth and walls adjacent to
the hearth should comply with the guidance on the separa�on of combus�ble material given in Building
Regula�ons Approved Document J and also in these stove instruc�ons.
If the stove is to be installed on a combus�ble (wooden) floor, it must be covered with a non-combus�ble material
at least
12 mm thick
, in accordance with Building Regula�ons Approved Document J, to a distance of
30 cm in
front of the stove
and
15 cm to each side
measuring from the door of the combus�on chamber.