Insert the cable or wires through the wall box and cut

to allow adequate length, strip the cable sheath as

desired, strip the individual wires to the lengths indi-

cated in Table 3, and twist the strands of each con-

ductor together. Back out the terminal screws on the

receptacle (or inlet) far enough (but not completely)

to allow the conductors to pass, insert the conductors

fully into their respective terminals and hand tighten

the terminal screws to the torque indicated in Table 4.

Assemble the receptacle (or inlet) and the color-

coded gasket to the box with the appropriate hardware.

Assemble the mating plug (or receptacle) to the cord

end as indicated in the assembly instructions above

for in-line connections, except there will be no finger

drawplate or associated black gasket.

Hole Pattern for Custom Mounting

In applications where custom mounting to a panel or

box is being performed, the clearance and mounting

holes should be drilled as indicated in the following

diagram and Table 5.

In order to maintain the NEMA 4X or IP 66 & 67 pro-

tection provided by DSN models in custom installa-

tions, watertight seals should be used under the

heads of the four mounting bolts and they must be

retained by a lock washer and nut on the inside of

the box or panel. Alternatively, four blind holes may

be drilled and threaded to accommodate the mount-

ing screws, provided that the hole depth is sufficient

to achieve adequate gasket compression.

OPERATION

To ensure safe and reliable operation Meltric plugs

and receptacles must be used in accordance with

their assigned ratings. They can only be used in

conjunction with mating receptacles or plugs manu-

factured by Meltric or another licensed producer of

products bearing the

TM

Quality Label.

Meltric plugs & receptacles are designed with differ-

ent keying arrangements, so that only plugs and

receptacles with compatible contact configurations

and electrical ratings will mate with each other.

Connection

To connect a plug and receptacle, first depress the

pawl to open the lid on the receptacle, then orient the

plug as shown in figure 1 so that the red dot on the

outside of the casing lines up with the red dot just to

the left of the latch on the receptacle casing. Push

the plug partially into the receptacle until it hits a

stop, then rotate the plug in the clockwise direction

until it hits another stop after about 30° of rotation.

At this point, the circuit is still open. Push the plug

straight into the receptacle as shown in figure 2 until

it becomes securely latched in place. The electrical

connection is now made. On in-line connectors,

squeeze the drawplates on both sides of the device

together until the plug latches in place.

Disconnection

To break the connection, simply depress the pawl as

shown in figure 3 . This will break the circuit and

eject the plug straight out to the rest, or off, position.

The plug contacts are de-energized at this point. To

remove the plug, rotate it counter-clockwise (about

30°) until it releases from the receptacle as shown in

figure 4 . Close and latch the lid on the receptacle.

Achieving Rated Watertightness

Rated ingress protection applies to the device when

the plug and receptacle are mated and latched

together. It also applies to the receptacle when the

lid is latched closed.

Lockout Provisions

All DS and DSN plugs are provided with lockout pro-

visions. To lockout the plug, insert a locking device

through the hole provided in the casing. This will

prevent the plug from being inserted into a receptacle.

DS and DSN receptacles may be purchased with

optional lockout provisions. To lockout the receptacle,

close and latch the lid and then attach the locking

device through the hole provided in the pawl. This

will prevent the lid from being opened for the inser-

tion of a plug.

NOTE:

Attaching the receptacle locking device with

the receptacle lid open will not prevent the insertion

of a plug. Lockout of the receptacle is only accom-

plished when the lid is locked closed.

MAINTENANCE

Meltric products require little on-going maintenance.

However, it is a good practice to periodically perform

the following general inspections:

• Check the mounting screws for tightness.
• Verify that the weight of the cable is supported

by the strain relief mechanism and not by the

terminal connections.

• Check the IP gaskets for wear and resiliency.

Replace as required.

• Verify the electrical continuity of the ground circuit.
• Check the contact surfaces for cleanliness and

pitting.

Deposits of dust or similar foreign materials can be

rubbed off the contacts with a clean cloth. Sprays

should not be used, as they tend to collect dirt. If

any significant pitting of the contacts or other serious

damage is observed, the device should be replaced.

Receptacle contacts may be inspected by a qualified

electrician. This should only be done with the power

off. It is accomplished by depressing the numbered

ring around the circumference of the interior on two

opposite points. This will allow the shutter to be

manually turned clockwise as required to permit

access to the contacts. Once the inspection is com-

plete, the shutter

must

be rotated counter-clockwise

until it is locked in the closed position.

MANUFACTURER’S RESPONSIBILITY

Meltric’s responsibility is strictly limited to the repair

or replacement of any product that does not conform

to the warranty specified in the purchase contract.

Meltric shall not be liable for any penalties or conse-

quential damages associated with the loss of produc-

tion, work, profit or any financial loss incurred by the

customer.

Meltric Corporation shall not be held liable when its

products are used in conjunction with products not

bearing the

TM

Quality Label. The use of

Meltric products in conjunction with mating devices

that are not marked with the

TM

Quality

Label shall void all warranties on the product.

Meltric Corporation

is an ISO 9001 certified company.

Its products are designed, manufactured and rated in

accordance with applicable UL, CSA and IEC stan-

dards. Meltric is also a member of BECMA, the inter-

national Butt-contact Electrical Connectors

Manufacturers’ Association. Like all members,

Meltric additionally designs and manufactures its

products in accordance with BECMA standards

established to ensure intermatablility with similarly

rated products manufactured by other members.

www.becma.ch

C

A

B

B

Table 5 - Custom Mounting Dimensions

‘A’

‘B’

C

Model

Inches mm Inches mm Inches mm

DSN20

-Recept

2.00

51

1.65

42

.19

5

DSN30

2.25

57

1.89

48

.19

5

DSN60

2.50

64

2.17

55

.19

5

DS20

2.25

57

1.89

48

.19

5

DS30

2.50

64

2.17

55

.19

5

DS60&DS100C 3.25

83

2.59

66

.22

5.5

DS100

4.00 102 3.20

81

.22

5.5

DS200

4.50 114 3.86

98

.28

7

INSDS/DSN 072408 E