MTS3610 Installation Guide
Mellanox Technologies
Rev 1.2.2
7
Ground Connections
Make sure to connect the ground post to a valid electrical ground. Use a grounding lug and a ground wire of
sufficient capacity to safely convey a potential discharge. The chassis is concurrently grounded through each
of the PSUs. Only connect the PSU cords to properly grounded outlets. Do not rely on the PSU grounds. It is
absolutely necessary to connect the grounding post. Make sure the connections are solid and permanent.
Figure 10: Ground Connection
Installing the Cable Holder
Holes for
connecting
the cable
holder to the
rack
X 8
Left side
rack
Top side
X 8
Right side rack
Bottom side
Step 1.
Place the Cable holder next to the rack and identify the holes for the caged nuts. The numbers
on the cable holders should face each other.
Step 2.
Put the caged nuts into the previously identified holes in the rack.
Grounding
post
Grounding
post
Grounding lug