4. Technician settings (cont’)
- 24 -
P35 – Enable/Disable Freeze protection
“01” -
Enable freeze protection (default)
“00” -
Disable freeze protection
P36 – Freeze protection cut-in set point
Range: 8...15°C / 46…59°F
Default: 8°C / 46°F
P37 – Freeze protection cut-out set point
Range: 10...17°C / 50…63°F
Default: 10°C / 50°F
P40 – View filter counter (hours) – Read only
Range: 0…999
hours
P41 – Reset filter time
“00” -
No action - keep counting (default)
“01” -
Reset filter counter
P42 – Adjust filter alarm delay time counter (hours)
Range: 0…999
hours
Default: 0 hours (0 = Disable)