Press the button to return to parameter P1 or wait 60
seconds to exit technician settings and return to normal display.
P200 – Restore defaults
Press the button to restore defaults
Press the button twice to return to normal display
4. Technician settings (cont’)
- 35 -
P182 – CO
2
Set point (activate fresh air damper)
Range: 600…2000 ppm (display shows value divided by 10)
Default: 750 ppm
P183 – CO
2
Band
Range: 100…500 ppm (display shows value divided by 10)
Default: 250 ppm
P184 – CO
2
High limit alarm set-point
Range: 600…2500 ppm (display shows value divided by 10)
Default: 1500 ppm
P185 – Display the CO
2
High limit alarm
0 – Do not show indication on display
1 – Show indication on display
P198 – Protocol indication (read only!)
0 - MODBUS
1 - BACnet