ETN24-P/PD-FC-SUPER2 

Owner's Manual - Installation and 

Operating Instructions

 

 

 

 

Meitav-tec Ltd (Contel group)

 

Tel: +972-3-9626462   Fax: +972-3-9626620

 

www.meitavtec.com - [email protected]

 

Rev. 1 | 04.08 

Summary of Contents for ETN24-P-FC-SUPER2

Page 1: ...ETN24 P PD FC SUPER2 Owner s Manual Installation and Operating Instructions Meitav tec Ltd Contel group Tel 972 3 9626462 Fax 972 3 9626620 www meitavtec com support meitavtec com Rev 1 04 08 ...

Page 2: ...and use Index Introduction 1 Options Accessories 2 Installation Instructions 3 Wiring Connections 4 DIP switch Configuration 5 External Sensor Connection 6 Change over Sensor Connection 7 Technician Settings 8 Operating Manual 9 RT03 Remote Control Option 10 ...

Page 3: ...In P configuration there are 2 separate outputs 1 for Cool and 1 for Heat 0 10VDC ideal for 4 pipe systems 2 Options and Accessories Remote sensor option TS01 Temperature Sensor with 0 8 meter cable RS01 Remote temperature Sensor Wall mount into decorative box RS02 Average temperature Sensor Wall mount into decorative box 2 required RT03 Hand held remote control For details on where to purchase ac...

Page 4: ...m temperature the module should be placed where the temperature is representative of the general room conditions Cold or warm air draughts radiant heat and direct sunlight should be avoided General points to follow Disconnect power to the main board before installing the unit The unit should not be installed on an outside wall or where there is an air draft The unit must not be exposed to a direct...

Page 5: ...and pull the back panel out B Line the back panel up against the wall or flat surface Install three screws as required C Make electrical connections as shown on enclosed electrical wiring diagram D Install the cover to the back panel first the two tabs on the bottom and then the top tongue Push until tight against the wall ...

Page 6: ...6 4 Wiring Connections ...

Page 7: ...7 5 DIP switch Configuration The DIP switches are located at the bottom right of the board as shown in the drawing 1 Default x Not applicable S2 Y2 FD S1 ...

Page 8: ...tat The length of the cable for the external sensor is 30 meters with standard cable If longer distance is needed then the cable MUST be shielded 7 Change over Sensor Connection For PD configuration only Disconnect power to the thermostat 24VAC Connect the change over Sensor to terminals T2 0 Reconnect power to the thermostat When the change over sensor is connected the Mode button will not be act...

Page 9: ...ional output range 0 10VDC or 2 10VDC and offset for temperature readings Note If no key is pressed for 5 seconds the thermostat will automatically return to normal display mode Enter settings Set temperature to 10 C 50 F Press and hold the Mode button 15 seconds to enter settings Cool will appear on display and SET will flash Set temperature limit for cool and heat Adjust the temperature limit fo...

Page 10: ... equals the differential Demand ambient temp set temp Differential range 2 C 10 C 4 F 18 F default 2 C 4 F Press the Mode button again a number will appear on display Adjust the differential using the or buttons Proportional outputs range 0 10VDC or 2 10VDC Press the Mode button again a number will appear on display Using the button change the scale to 2 10VDC 2 will appear on display Using the bu...

Page 11: ...on to activate he thermostat The word ON will appear on display Press and hold the On Off button 3 seconds to deactivate the thermostat The word OFF will appear on display Temperature set point adjustment Press the or buttons the set point temperature will flash and SET will appear on display Adjust the set point temperature using the or buttons ...

Page 12: ...r Cool and Heat will appear on display Available in P configuration only see DIP switch configuration In Auto change over mode the active mode will flash Fan Only Fan will appear on display Fan Speeds in 2 or 3 speeds configuration only Press the Fan button to switch between Low Speed Lo will appear on display Medium Speed Me will appear on display High Speed Hi will appear on display Auto Speed H...

Page 13: ...d in 2 or 3 speeds configuration In Auto Fan mode the fan will run only during demand for cooling or heating Press the fan button again to cancel the Auto Fan mode Press and hold in 2 or 3 speeds configuration Lock Unlock Set the temperature to anything but 10 C 50 F Press and Hold the Mode button 20 seconds to lock the thermostat s buttons Press and Hold the Mode button again to unlock the thermo...

Page 14: ...14 10 RT03 Hand Held Remote Control Non Program Option General ...

Page 15: ...ust the minutes using the or buttons Press the Select button again to return to normal display Press the On Send button to send information to the thermostat Timer Start Time Press the Select button twice PROGRAM START will flash on display Press the Select button the hours will flash Adjust the hours using the or buttons Press the Select button the minutes will flash Adjust the minutes using the ...

Page 16: ...to send the information to the thermostat Batteries Replacement When the batteries are low the display of the remote control will dim If the batteries will not be replaced the display will turn off completely Pull the batteries cover down to reveal the batteries Remove the old batteries Wait for 10 minutes before installing the new batteries Install two new AAA batteries Pay attention to the polar...