4. DIP Switch Configuration
Before making any changes disconnect power to the main board.
Table 4.1 – DIP Switch Selection
Switch Function
ON OFF
Default
Internal Sensor Control
X
1
External sensor control
X
ON
2 Not
in
use OFF
Electrical Heat
X
3
Oil/Gas Heat
X
OFF
3 minutes compressor delay
X
4
Without delay (for test only)
X
OFF
Internal Sensor Control
X
5
External sensor control
X
OFF
Internal Sensor Control
X
6
External sensor control
X
ON
Use this table together with the illustration above showing the switch configuration.
Default DIP switch configuration:
ON
1 2 3 4 5 6