Megmeet MTCW Series Quick Start Manual Download Page 3

3

Item

Indicator

Input
signal

Thermocouple
type

K、J、E、N、T、R、S、B

Thermal
resistance
type

Pt100、Cu100、JPt100、Cu50、Ni120

Input
method

Transistor
output with
open gate

Power supply voltage circuit: 5V ~ 24V;
The maximum circuit power supply voltage
circuit: 30V; Loop current: 0.3A /24Vdc;
Leakage current when open:<0.1mA/30Vdc;
Minimum load:5mA(5Vdc~24Vdc)

The sampling period

About 100 ms

Control
cycle

Fast

1~100,the unit is 0.1s.The specific
value is determined by the
characteristics of the temperature
controlled object

Slow

1~100,the unit is 1s.The specific value
is determined by the characteristics of
the temperature controlled object

Control method

ON/OFF,hand,single PID control

Rated
temperature
range

Type K

-100℃~1200℃(-148℉~2192℉)

Type J

-100℃~1200℃(-148℉~1112℉)

Type E

-100℃~850℃(-148℉~1562℉)

Type N

-100℃~1200℃(-148℉~2192℉)

Type T

-200℃~300℃(-328℉~572℉)

Type R

0℃~1600℃(32℉~2912℉)

Type S

0℃~1600℃(32℉~2912℉)

Type B

400℃~1800℃(752℉~3272℉)

Pt100

-150℃~600℃(-238℉~1112℉)

JPt100

-150℃~500℃(-238℉~932℉)

Cu100

-30℃~120℃(-22℉~248℉)

Cu50

-30℃~120℃(-22℉~248℉)

Ni120

-80.0℃~280.0℃(-112.0℉~536.0℉)

Accuracy

Thermocouple

Input range ± 0.3%, ambient temperature
compensation error <=2℃

Thermal

resistance

Input range ±0.5%

Isolation

The sampling channel is isolated from the
power supply, the sampling channel is
isolated from the output, and the
channels are not isolated from each other

5.3 Communication specification

Name

Communication

protocol

Port remark

Communication

method

COM0

Modbus

A0,B0

RS485

COM1

Modbus

A1,B1

RS485

WAN

Modbus and Modbus

TCP

WAN

ETHERNET

5.4 Indicator description

Name

Status

Indicator

PWR

ON

24V power turn on

RUN

Flashes quickly

(10Hz~15Hz)

Normal

Flashes slowly
(0.5Hz~1Hz)

There is an error. See #3612 and

#3613 for the error status

COMM or COMM0

Flashes

COM0 is communicating

COMM1

Flashes

COM1 is communicating

Y01~Y16

ON

The corresponding channel output is

ON

6. BFM

The module USES Modbus to exchange temperature data and other

information with the main module through BFM. A cache of read and

write attributes can be read and written using the MODBUS directive.

MODBUS supports 01, 03, 05, 06 and 16 functions. 01, 05 function

code to the bit register operation, 03, 06, 16 function code to the

integer register operation, if read reserved unit, will get 0 value. With

MODBUS protocol, up to 100 BFM units can be read and written at one

time.

Note: MTCW series thermostat support MTC series thermostat BFM

area.

Function

CH1

CH2

CH3

CH4

CH5

CH6

CH7

CH8

CH9

CH10 CH11 CH12 CH13 CH14 CH15 CH16

Measured value(PV)

1500 1501 1502 1503 1504 1505 1506

1507

1508 1509 1510 1511 1512 1513 1514

1515

Heating side control

output(MV)

1532 1533 1534 1535 1536 1537 1538

1539

1540 1541 1542 1543 1544 1545 1546

1547

Multi-step control of

current execution step

1564 1565 1566 1567 1568 1569 1570

1571

1572 1573 1574 1575 1576 1577 1578

1579

Working status word

1596 1597 1598 1599 1600 1601 1602

1603

1604 1605 1606 1607 1608 1609 1610

1611

Digital filter set of

one step

1628 1629 1630 1631 1632 1633 1634

1635

1636 1637 1638 1639 1640 1641 1642

1643

D0

1788 1789 1790 1791 1792 1793 1794

1795

1796 1797 1798 1799 1800 1801 1802

1803

D1

1820 1821 1822 1823 1824 1825 1826

1827

1828 1829 1830 1831 1832 1833 1834

1835

A0

1724 1725 1726 1727 1728 1729 1730

1731

1732 1733 1734 1735 1736 1737 1738

1739

A1

1756 1757 1758 1759 1760 1761 1762

1763

1764 1765 1766 1767 1768 1769 1770

1771

Input type

1660 1661 1662 1663 1664 1665 1666

1667

1668 1669 1670 1671 1672 1673 1674

1675

Set value(SV)

1692 1693 1694 1695 1696 1697 1698

1699

1700 1701 1702 1703 1704 1705 1706

1707

Proportional cycle

time

1852 1853 1854 1855 1856 1857 1858

1859

1860 1861 1862 1863 1864 1865 1866

1867

Heat side proportional

band

1884 1885 1886 1887 1888 1889 1890

1891

1892 1893 1894 1895 1896 1897 1898

1899

Heat side integral

time

1916 1917 1918 1919 1920 1921 1922

1923

1924 1925 1926 1927 1928 1929 1930

1931

Heat side derivative

time

1948 1949 1950 1951 1952 1953 1954

1955

1956 1957 1958 1959 1960 1961 1962

1963

Control action

1980 1981 1982 1983 1984 1985 1986

1987

1988 1989 1990 1991 1992 1993 1994

1995

Heat/cool action

2012 2013 2014 2015 2016 2017 2018

2019

2020 2021 2022 2023 2024 2025 2026

2027

Hand output value

2044 2045 2046 2047 2048 2049 2050

2051

2052 2053 2054 2055 2056 2057 2058

2059

Adjust sensitivity

2076 2077 2078 2079 2080 2081 2082

2083

2084 2085 2086 2087 2088 2089 2090

2091

Auto-tuning deviation

2108 2109 2110 2111 2112 2113 2114

2115

2116 2117 2118 2119 2120 2121 2122

2123

Step 1 temperature

2140 2141 2142 2143 2144 2145 2146

2147

2148 2149 2150 2151 2152 2153 2154

2155

Step 2 1temperature

2172 2173 2174 2175 2176 2177 2178

2179

2180 2181 2182 2183 2184 2185 2186

2187

Step 3 temperature

2204 2205 2206 2207 2208 2209 2210

2211

2212 2213 2214 2215 2216 2217 2218

2219

Step4 temperature

2236 2237 2238 2239 2240 2241 2242

2243

2244 2245 2246 2247 2248 2249 2250

2251

Step 5 temperature

2268 2269 2270 2271 2272 2273 2274

2275

2276 2277 2278 2279 2280 2281 2282

2283

Step 6 temperature

2300 2301 2302 2303 2304 2305 2306

2307

2308 2309 2310 2311 2312 2313 2314

2315

Step 7 temperature

2332 2333 2334 2335 2336 2337 2338

2339

2340 2341 2342 2343 2344 2345 2346

2347

Step 8 temperature

2364 2365 2366 2367 2368 2369 2370

2371

2372 2373 2374 2375 2376 2377 2378

2379

Step 1 time

2396 2397 2398 2399 2400 2401 2402

2403

2404 2405 2406 2407 2408 2409 2410

2411

Step 2 time

2428 2429 2430 2431 2432 2433 2434

2435

2436 2437 2438 2439 2440 2441 2442

2443

Step 3 time

2460 2461 2462 2463 2464 2465 2466

2467

2468 2469 2470 2471 2472 2473 2474

2475

Step 4 time

2492 2493 2494 2495 2496 2497 2498

2499

2500 2501 2502 2503 2504 2505 2506

2507

Step 5 time

2524 2525 2526 2527 2528 2529 2530

2531

2532 2533 2534 2535 2536 2537 2538

2539

Step 6 time

2556 2557 2558 2559 2560 2561 2562

2563

Summary of Contents for MTCW Series

Page 1: ...r cabinet wall above and below shall be no less than 20cm Installation in other directions is not conducive to the product itself heat and the product under the heat must not have equipment Install and fix with DIN slot DIN slot of 35mm width can be used for installation under low vibration environment Open the DIN clasp at the bottom of the module and clip the bottom of the module on the DIN guid...

Page 2: ...e electromagnetic interference Using long cables connecting cables is susceptible to noise interference It is recommended to use cables less than 100 meters in length connecting cables The cable connecting cable has impedance which will introduce measurement error The characteristic adjustment can solve this problem The thermal resistance must be connected by a three wire system It is recommended ...

Page 3: ...king status word 1596 1597 1598 1599 1600 1601 1602 1603 1604 1605 1606 1607 1608 1609 1610 1611 Digital filter set of one step 1628 1629 1630 1631 1632 1633 1634 1635 1636 1637 1638 1639 1640 1641 1642 1643 D0 1788 1789 1790 1791 1792 1793 1794 1795 1796 1797 1798 1799 1800 1801 1802 1803 D1 1820 1821 1822 1823 1824 1825 1826 1827 1828 1829 1830 1831 1832 1833 1834 1835 A0 1724 1725 1726 1727 172...

Page 4: ...25 3526 3527 3528 3529 3530 3531 PID output dead band 3548 3549 3550 3551 3552 3553 3554 3555 3556 3557 3558 3559 3560 3561 3562 3563 Hand automatic smooth transfer 3580 3581 3582 3583 3584 3585 3586 3587 3588 3589 3590 3591 3592 3593 3594 3595 Error status word system error 3612 Error status word broken even error 3613 Set value range error address 3616 3617 Channel characteristics confirmation c...

Page 5: ...ough cables respectively Communication mode RS485 communication protocol MODBUS 3 Because the default communication parameters are the same so the connection can automatically communicate 4 MTCW 16NN can be controlled by BFM area or temperature control assistant 9 Common problems and solutions When the module does not work properly please check in turn 1 the connection of the power line and the co...

Page 6: ...perate according to the user s manual 2 Machine damage caused by fire flood abnormal voltage etc 3 Damage caused when a programmable controller is used for unusual functions 4 Self disassembly programmable controller 5 The service fee shall be calculated according to the actual cost If there is another contract the contract shall take precedence 6 If you have any problem you can contact the agent ...