Sensor type
and
temperature
range

Pt100

150

℃~

600

℃(-

238

℉~

1112

℉)

JPt100

150

℃~

500

℃(-

238

℉~

932

℉)

Cu100

30

℃~

120

℃(-

22

℉~

248

℉)

Cu50

30

℃~

120

℃(-

22

℉~

248

℉)

Ni120

80.0

℃~

280.0

℃(-

112.0

℉~

536.0

℉)

Thermal resistance

Input range±0.5

7.2.4 TC input channel specifications
Item

Index

Input single

Thermocouple
type

K

J

E

N

T

R

S

B

Output
method

Transistor
output with
open gate

Loop power voltage

5V

24V

Max.

Power voltage of loop

30V

Loop

current

0.3A/24Vdc

Leakage current

when open

: <

0.1mA/30Vdc

Min.

load

5mA

5Vdc

24Vdc

The sampling period

About 100ms

Temperature control cycle

1

100

unit 1s

The specific value is

determined by the characteristics of

the temperature control object

Control method

ON/OFF control

Hand control

single

PID control

Rate
temperature
range

K type

100

℃~

1200

℃(-

148

℉~

2192

℉)

J type

100

℃~

1200

℃(-

148

℉~

1112

℉)

E type

100

℃~

850

℃(-

148

℉~

1562

℉)

N type

100

℃~

1200

℃(-

148

℉~

2192

℉)

T type

200

℃~

300

℃(-

328

℉~

572

℉)

R type

0

℃~

1600

℃(

32

℉~

2912

℉)

S type

0

℃~

1600

℃(

32

℉~

2912

℉)

B type

400

℃~

1800

℃(

752

℉~

3272

℉)

Accuracy

Thermocouple Input

range

±0.3

Ambient

temperature compensation error<=2

Thermal

resistance

Input range

±0.5

Isolation

Channels are isolated from each

other

8. Common problems and solutions

When the module cannot work normally, please check in turn:
(1) The connection of power lines and the status of related switches
and protective appliances to ensure that the module has been reliably
supplied;
(2) Whether the connection of user terminals is firm;
If the above inspection is still unable to work, you can refer to the
following table.

phenomenon

Possible reason

Countermeasures

RUN and ERR are
OFF

Out of voltage or low
voltage

Check power supply
condition and
exclude

The power switch is
off or the fuse is
blown

Check the condition
of switches, wires or
fuses to exclude
them

Abnormal

power

connection

Power plate damage

Check and confirm
whether the voltages
between 24V+ and
24V- terminals are in
normal range

RUN and ERR are
flashed intermittently
in the same time

The power supply is
unstable
The

module

is

damage

RUN is OFF

Shut down remotely
by upper computer
equipment

Make the upper
computer start up
remotely

System error outage

Check by assistant

ERR single light is
ON

System error outage

Check with an
assistant and consult
the errata manual

1. Warranty scope refers to the programmable controller body.
2. The warranty period is 18 months. If the product breaks down or is
damaged during normal use, our company will repair it free of charge.
3. The warranty period starts from the date the product is manufactured.
Machine code is the only basis for judging the warranty period.
Equipment without machine code shall be treated as under warranty.
4. Even within the warranty period, a maintenance fee will be charged
if:

Failure of the machine caused by failure to operate in
accordance with the user's manual.

Damage to machinery caused by fire, flood, abnormal voltage,
etc.

Damage caused when a programmable controller is used for
abnormal functions.

Self-disassemble the programmable controller.

5. The service fee shall be calculated according to the actual cost. If
there is another contract, the contract shall take precedence.
6. If you have any questions, please contact the agent or our company
directly.