DD = I

1min

/(V x C) 

  

 
where 

I

1min

 is the discharge current in mA one minute after 

removal of the test voltage 

V

 in Volts and 

C

 is the capacitance in 

Farads. 

 

 

Homogenous insulation will have a DD value of 0, while good 
multi-layer insulation will have a value up to 2. The following table 
is a guide to DD test results:

 

 

Insulation Condition 

DD result 

Bad 

> 7 

Poor 

4 - 7 

Questionable 

2 - 4 

Good 

< 2 

Homogenous 

Step Voltage Test 

The SV test is a controlled overvoltage test that can be applied to 
stator and rotor windings on synchronous and asynchronous AC 
motors and the armature and field windings on DC motors. It is 
advisable to perform a PI test before an SV test to determine if 
the insulation is suitable for overvoltage testing. If a PI test was 
performed to verify the winding’s suitability for overvoltage testing, 
the winding must be completely discharged before an overvoltage 
test is performed. 
 
The SV test is based on the principle that an ideal insulator will 
produce identical readings at all voltages, while an insulator which 
is being over stressed, will show lower insulation values at higher 
voltages.  
 
The SV test is selected using SV mode switch position and any 
voltage range including V

L

 range setting. If no custom SV test 

has been setup then a standard five step test will be performed 
where each step is 1/5

th

 of the test voltage and 1/5th of the test 

time If a standard 5 step test is required at the V

L

 voltage, set timer 

1 to 0 sec. if a custom SV test has previously been setup.  
  
 

Rotary switch setting 
indicated: 

 
For a regular 5 step SV 
test, resistance readings 
for the first four ‘steps’ are 
displayed under 
consecutive time designators ‘1m’ to ‘4m’. The 5 minute reading is 
displayed by the main display. The standard SV test duration can be 
adjusted if desired from the 5 minute default value using the 
up/down arrows and OK to save the setting. If the default 5 minute 
test duration is changed by the user the four readings will not show 
the respective ‘1m’ to ‘4m’ indicators. 
For the standard five step SV test the step timer will always be set to 
total test time divided by 5.  Too short a step time may result in 
incorrect readings and too long a step time may over stress a motor. 
 
 A custom SV can be created with up to 10 steps. To set timing and 
voltages for  this test press the right arrow from within the timer 
setup for the SV test. The SV settings are adjusted using up and 
down arrows and confirmed by OK. The custom SV enables each 
step duration and test voltage to be set on up to 10 steps. When all 
required steps have been setup change the subsequent time to 0 
sec. To run the custom SV test, the mode switch is set to SV and 
main rotary switch to V

L

.

 

 
The reference standard for step voltage testing is IEEE 95-2002.  

Ramp Voltage Test 

The ramp voltage test is an overvoltage test similar to the SV test 
but with many very small steps. The slow continuous voltage ramp is 
less likely to result in unpredictable damage to the insulation than 
the rapid step increases employed in SV test.  

Summary of Contents for S1-1068

Page 1: ...S1 568 S1 1068 S1 1568 5 kV 10 kV 15 kV High Performance DC Insulation Resistance Testers USER MANUAL M...

Page 2: ...navoidable the user must take all necessary precautions This instrument is not intrinsically safe and must not be used in hazardous atmospheres If this equipment is used in a manner not specified by t...

Page 3: ...Directive The crossed out wheeled bin symbol on the instrument and on the batteries is a reminder not to dispose of them with general waste at the end of their life Megger is registered in the UK as...

Page 4: ...ime output during insulation tests 13 Bluetooth interface activation 14 PowerDB 15 Interfacing S1 and MIT ranges to PowerDB 15 Battery indicator 18 On screen error reporting 18 Error codes 18 Measurem...

Page 5: ...tions ensure highest quality resistance measurements All models support diagnostic and over voltage tests PI DAR DD SV and ramp test Remote Control RC mode via USB cable Bluetooth link for live stream...

Page 6: ...h associated HV warning lamp 8 Backlight button 9 Range rotary switch 10 Save button 11 Test mode rotary switch 12 LED indicating line power mains 13 Filter button 14 Display 15 Power socket 16 Functi...

Page 7: ...265 V rms ac at 50 60 Hz A green LED illuminates when line power mains is present The battery will charge over its operating temperature range as long as an AC source is connected except when a test...

Page 8: ...all models have a backlight button The mode rotary switch controls the insulation test type Basic insulation resistance IR timed insulation resistance IR t Dielectric Absorption Ratio DAR Polarisation...

Page 9: ...To test for high noise select the voltmeter function and read the voltage A high voltage will indicate a high noise environment Voltmeter A voltmeter is incorporated in the instrument and measures AC...

Page 10: ...istance of an insulator reaches this limit The default alarm setting is 500 k and inactive x is displayed on the right of the display Set range and mode switches to the settings and IR positions respe...

Page 11: ...etection and test voltage continues after breakdown of the insulation This enables the location of a failure to be detected but it is a destructive test Due to the potential damage that could occur th...

Page 12: ...is complete The save icon will appear momentarily to confirm the data is saved If a full test curve is required the user must select logging by pressing the save button before starting the test In th...

Page 13: ...er exists use it when starting PowerDB for the first time to find the S1 driver if not allow the operating system to search the internet for the driver When using the USB cable check the serial port a...

Page 14: ...on the S1 and the PC Let the PC find the S1 its serial number will be part of the identifier and default passcode for connection is 0000 Create a connection to the S1 and check the link works by conn...

Page 15: ...the version supplied on the product CD if the PC being used has no access to the internet The instrument does not need to be powered up to respond to the driver as it is powered via the USB cable Load...

Page 16: ...itialise the instrument An OK confirmation appears at the top of the form if communications have been successful Scroll down the PowerDB form until you see a table with cyan filled headers RIGHT CLICK...

Page 17: ...hree tables are available in the PowerDB form representing three phases named A B and C Tests listed in the Import Live Stream Control application listed under Test Info can be saved in any form by ex...

Page 18: ...the battery has failed On screen error reporting Should an error be detected during the operation of the S1 instrument an error code is reported preceded by Err with the read handbook warning Error co...

Page 19: ...is calculated and displayed Time Constant TC Rinsulation x Cinsulation Timed IR test A timed test IR t will automatically terminate an insulation test after a preset time Default timer is set to 1 mi...

Page 20: ...developed by EDF France s power utility company it is a diagnostic insulation test that allows ageing deterioration and voids in the insulation to be assessed The result is dependent on the discharge...

Page 21: ...required at the VL voltage set timer 1 to 0 sec if a custom SV test has previously been setup Rotary switch setting indicated For a regular 5 step SV test resistance readings for the first four steps...

Page 22: ...kV is recorded and can be read into PowerDB PowerDB Lite or converted to a spreadsheet so that the current vs voltage curves can be compared to published curves in IEEE 95 2002 Remote control mode Rem...

Page 23: ...total current has four components capacitive current absorption current conductance current and leakage current If a generator has wet or contaminated windings conductance current will be present In...

Page 24: ...red by the instrument and used to calculate resistance This technique is only permissible if the item under test is isolated from ground In this context isolated means insulated by a resistance of at...

Page 25: ...same potential as the negative terminal Since the leakage resistance is effectively in parallel with the resistance to be measured the use of the guard causes the current flowing through surface leak...

Page 26: ...nd all other equipment before opening the case to change the battery The instrument must not be operated with the case open DANGER Hazardous voltages are exposed with the mains connected and the case...

Page 27: ...hange the battery 2 Always replace both battery packs together 3 The instrument must not be operated with the case open DANGER Hazardous voltages are exposed with an AC source connected and the case o...

Page 28: ...1068 10 k to 35 T S1 1568 10 k to 35 T Accuracy 23 C S1 568 5000 V 2500 V 1000 V 500 V 250 V 5 to 1 T 500 G 200 G 100 G 50 G 20 to 10 T 5 T 2 T 1 T 500 G S1 1068 10000 V 5000 V 2500 V 1000 V 500 V 5 t...

Page 29: ...z 65 Hz Timer range 99 m 59 s 15 s minimum setting Memory capacity 11 hrs logging 5 sec intervals Test regimes IR IR t DAR PI SV DD ramp test Interfaces USB type B device Bluetooth Real time output re...

Page 30: ...8579 Fax 1 610 676 8625 Megger operate fully traceable calibration and repair facilities ensuring your instrument continues to provide the high standard of performance and workmanship you expect These...

Page 31: ...Page 31 Approved Service Centres A list of Approved Service Centres may be obtained from the UK address above or by contacting Megger on ukrepairs megger com and giving details of your location...

Page 32: ...dium insulated clips 1002 531 Shielded USB cable PowerDB Lite software CD Remote control indicator dongle S1 1068 only 3 m leadset x 3 large insulated clips 1002 534 S1 1568 only 3 m 15 kV leadset x 3...

Page 33: ...S France T 33 0 1 30 16 08 90 F 33 0 1 34 61 23 77 E infos megger com Megger AB Box 724 182 17 Danderyd Sweden T 46 8 510 195 00 F 46 8 510 195 95 Megger Pty limited Unit 1 11 21 Underwood Road Homebu...

Reviews: