background image

Getting started

Appliance test 

socket 110 V 

Flash test socket 

(PAT 350 only)

Firmware  

upgrade port

Power off / 

Escape and 

Home keys

Test keypad – 

See Test key layout 

Extension lead 

/ IEC lead test 
socket

Appliance test 

socket (230 V)

Fuse checker

Display

Display 

navigation

UP/DOWN/

LEFT/RIGHT 

and OK

TEST button

Earth bond and 

insulation 

test probe socket

NOTE: Do not connect any equipment until the PAT tester 
has been switched on and passed a self test. 

Instrument and test key layout

test probe socket

Lead null 

post

           Note: The PAT320 does not include the Flash test option.

           Note: The PAT320 does not include the Flash test option.

Quick Start guide

                                                         

M

PAT300 Series Portable Appliance Testers

G

Safety Warnings and symbols used

The following safety warnings and precautions 

must

 be read and understood before 

the instrument is used. They must be observed during use.

For safety, only connect the PAT to a supply that is properly earthed. If in doubt,    

  the supply should be checked by a qualifi ed electrician.

Do not use

 the instrument if there are any signs of damage.

  All test leads, probes and clips must be in good order, clean and with no broken or  

  cracked insulation.

  Probes and clips should be held behind the fi nger guard. 

  Test leads not used during a measurement should be disconnected from the  

 

  appliance tester.

  For dual voltage testers, both sockets can be live simultaneously.

  Only connect one asset to the PAT during testing.

  Tests should be carried out in the order recommended below. An appliance that    

  fails a test should be repaired before further testing is carried out.
Recommended Sequence:
1.  Earth Bond/ Continuity of the protective earth conductor (Class I devices)
2.  Insulation test (or earth leakage)
In addition further tests can be performed 
3.  Operation test
4.  Leakage test

  Only perform an operational test after the earth bond and insulation tests  

 

  have been completed, as this test operate at mains voltage.

  During testing, ensure no hazard will exist as a result of normal running or  

 

  under fault conditions.

  During testing the unit under test (asset) should not be touched, other than  

 

  using the appropriate accessories, as faulty appliances can present a shock  

 

  hazard.

  Do not touch the exposed parts of test leads during tests as hazardous  

 

  voltages may be present due to potentially faulty appliance.

  Do not touch the IEC extension lead socket pins especially during a test, as  

 

  hazardous voltages may be present due to a potentially faulty appliance

  Assets should not be routinely Flash tested. Where fl ash testing is required,  

 

  refer to further guidance on Flash testing, section 4.5.

  Replacement fuses must be of the correct rating and type. Refer to section 6.3 

  The USB connection should only be used by approved service personnel,  

 

  nothing should be connected to the USB port during testing.

  Only use NiMH rechargeable 9V PP3 battery, do not use a non rechargeable type 

           Note: The PAT320 does not include the Flash test option.

           Note: The PAT320 does not include the Flash test option.

  as this could become dangerous if charged by the instrument.

  Serviceable fuses should only be replaced with those that are suitably rated 

  In case of an emergency use an easily accessible power point

Safety symbols used on the instrument

F

  

Caution: risk of electric shock

G

  

Caution: refer to accompanying notes.  When displayed at the start of an  

 

   

insulation test, warns that a hazardous voltage may exist at the test lead  

 

   

probes

Equipment complies with the relevant EU Directives

Fuse
HV test lead in unlocked position
HV test lead in locked postion
Battery type fi tted

DO NOT connect to 230 V supply

Battery function  - 

A 9 V PP3 rechargeable NiMH battery is fi tted to allow fast 

restart should the PAT be unplugged and reconnected to an electrical supply in less 
than 5 minutes.

Battery replacement

Warning: 

Do not switch the instrument on with the battery  cover removed  

 

or test leads connected.

Only use NiMH rechargeable batteries.

 

1.  Switch off the instrument and disconnect the instrument from any electrical    

 

  circuits.

 

2.  Remove the battery cover.

 

3.  Remove the old battery and refi t a new one, observing the terminal polarity.

 

4.  Replace the cover and retaining screw.

           Note: The PAT320 does not include the Flash test option.

  All test leads, probes and clips must be in good order, clean and with no broken or  

Test group 1 to 5  

Description

1  Class I test 

For testing assets with an earth return conductor

2  Class II test 

For testing assets without an earth return conductor

3  IEC lead and   For testing extension leads and IEC type power leads  

  Extension   

(found on computers, kettles etc)

  lead test 

4  RCD tests 

For testing Plug-in RCDs and extension leads fi tted  

   

with RCDs

5  Information 

Provides technical support details

Individual tests 6 to 10

6  Bond 

Ω

Performs an earth bond/continuity test at 200 mA, 

   

10 A or 25 A

7  INS M

Ω

Performs an insulation test at either 250 V or 500 V

8  LEAK mA 

Performs an earth leakage test

9  LOAD VA 

 Performs a RUN test and measures the power drawn

10 1.5 kV/3 kV 

Performs a fl ash test at the required voltage

Test key layout

Test groups summary

Fuse replacement

Warning:  Do not switch the instrument on with the fuse cover 
removed or test leads connected.

 

1.  Switch off the instrument and disconnect (the instrument) from any 

 

  electrical circuits.

 

2.  Remove the fuse cover.

 

3.  Replace the blown fuse with the correct type and rating.

 

4.  Replace the fuse cover.

1

2

3

4

5

6

7

8

9

10

Reviews: