background image

APPLICATIONS 

ELECTRICAL CONTRACTORS FEATURES AND
APPLICATIONS

The LCB2000/2 and LCB2500/2 are designed to provide
the electrical contractor with highly professional tools for
testing and commissioning fixed installations to both the
British and International Wiring Regulations.  The
LCB2000/2 provides a comprehensive set of features to
cater for almost all Loop and RCD testing needs.  The
LCB2500/2 adds to these the ability to store and print
results on site and to view R1 + R2 loop values during a
live test.  The on-board storage facilities enable each test
result to be assigned to particular distribution board and
circuit references.  Data may be later recalled to the
display for manual completion of certificates of test or for
maximum performance downloaded to certification
software such as PowerSuite for Windows, PowerSuite
XPress or NICEone to create a seamless recording system
with the traceability necessary for safety critical applications.
Some of the key features of the LCB2000/2 and LCB2500/2
are:

Intelligent Power saving backlight

The inclusion of an intelligent backlight ensures 
that the display can be clearly seen even where 
the distribution board is located in a dark 
cupboard but without ruining battery life.

A choice of Non Tripping loop tests 

A three wire 15 mA non tripping loop test 
provides a fast response with 0,01 

. A two wire 

15mA non-tripping loop test is also included and 
provides 0.1 

resolution.  Both tests guarantee 

not to trip RCDs rated at 15 mA or more.

No neutral needed for Line - Earth Testing 

This useful feature enables tests to be performed 
on lighting and three phase delta configurations 
where no neutral is available.

Automatic Test Start

When using probes to make the connections 
both hands are needed making it almost 
impossible to press the test button.  The 
LCB2000/2 and LCB2500/2 include a “Test start 
on voltage detection” feature.  Once armed the 
instrument will wait until the probes are 
connected or voltage is turned on then 
automatically start a test . 

Three Phase Test Capability

Phase-Phase measurements (up to 440 V), Phase-
Neutral and Phase-Earth tests are all possible.

A variety of Test leads Supplied as standard

LCB2000/2 and LCB2500/2 are supplied with a 
pre-wired plug for making connections via the 
standard socket outlets and a three wire leadset 
with probes and clips.  This enables connection 
to be made easily to a wide variety of systems.

Selectable RCD Types

The LCB2000/2 and LCB2500/2 may be easily set 
to test General purpose, Selective or dc sensitive 
RCDs.

Tests Programmable RCDs

The Megger LCB2000/2 and LCB2500/2 cater for 
programmable RCDs by allowing the test current 
to be precisely defined up to 1000 mA.  This 
advanced feature enables the instruments to be 
used in a wide range of specialist installations, 
(e.g. medical), or where a programmable device 
is encountered.

Contact Voltage Indication

Megger LCB2000/2 and LCB2500/2  indicate the 
Contact Voltage, (potential that bonded 
metalwork would actually rise to in the event of 
a fault) and the loop impedance during and RCD 
test. 

Auto-Sequence RCD tests 

RCD testing requires a number of tests to be 
performed sequentially, many of which will trip 
the RCD which then has to be reset each time.  
In many cases the tester is some distance away 
from the RCD requiring the operator to make 
repeated journeys to reset the trip.  LCB2500/2 
includes an unique Auto-Sequence RCD enabling 
the operator to remain with the RCD in order to 
reset it whilst the instrument automatically cycles 
through the necessary tests and records the 
results ready for when the operator returns.

■ 

RCD Ramp Test - Indicates the actual tripping current 

There are numerous situations when it is useful 
to know the current at which a particular RCD 
actually trips.  For instance in cases of nuisance 
tripping it is necessary to establish whether the 
RCD is over sensitive.  LCB2000/2 and LCB500/2 
include a Ramp Test feature which automatically 
increases the test current until the RCD trips.  At 
this point the actual tripping current is displayed.

Phase Rotation Display

LCB2000/2 and LCB2500/2 include a special 
phase rotation symbol within the LCD display.  
When connected to a three phase supply the 
symbol automatically indicates the phase 
rotational sequence.

Warranty

In addition to the electrical features above the 
rugged design of the LCB2000/2 and LCB2500/2 
range ensures that they can withstand the 
everyday handling, transportation and storage 
with other tools in the contractor’s toolbag.  Both 
products are supplied with a three year 
manufacturer’s warranty.

LCB2000/2 AND LCB2500/2

Premium Loop & Circuit Breaker Testers

Summary of Contents for LCB2000/2

Page 1: ...of operation live display of R1 R2 values and efficiency provided by the downloading of data When combined with software certification the system provides a highly professional image for the contractor combined with the ever increasing requirement for traceability of test results The LCB2500 2 offers comprehensive data storage options with individual test results being quickly stored with relevant...

Page 2: ...plied with a pre wired plug for making connections via the standard socket outlets and a three wire leadset with probes and clips This enables connection to be made easily to a wide variety of systems Selectable RCD Types The LCB2000 2 and LCB2500 2 may be easily set to test General purpose Selective or dc sensitive RCDs Tests Programmable RCDs The Megger LCB2000 2 and LCB2500 2 cater for programm...

Page 3: ...e delayed Selective and d c Sensitive Nominal Supply 230 V 50 Hz Supply Range 100 280 V 45 65 Hz 1 2I n TEST CONTACT VOLTAGE Displayed range 0 V to 90 V Measurement range 5 V to 90 V LOOP RESISTANCE measured at 1 2 I n I n RESOLUTION 10 0 5 kΩ to 9 kΩ 30 170 Ω to 3 kΩ 100 50 Ω to 900 Ω 300 17 Ω to 300 Ω 500 10 Ω to 180 Ω 1000 5 Ω to 90 Ω 2 SECOND NO TRIP TEST at 1 2 I n optional Test current durat...

Page 4: ...t international directives concerning safety and electromagnetic compatibility The instruments meet the requirements for double insulation to IEC61010 1 1995 EN61010 1 1995 Safety Requirements for electrical equipment for measurement control and laboratory use Category III 300 Volts phase to earth ground and 440 Volts phase to phase without the need for separately fused test leads If required fuse...

Reviews: