MPB 90 Pro
12.
FEEDER MULTIPLIER
In this parameter, we set the value of the operation time of the Internal feeder regarding
the operations time of the External Feeder. The operation time of the internal feeder must
be enough, so the wood-pellet is supplied from the external feeder, to be driven by the
internal feeder to the burners fire chamber.
Manufacturer Advise: 1.5 – 2.5
13.
IGNITION STABILIZATION
When ignition has occurred, the air-fan works for the time is set by this parameter. This
operation drives the ignition gases out of the boiler faster.
Manufacturer Advise:
10-30sec
14.
MAINTAIN STABILIZATION
When the burner goes from work mode to maintain mode, the air fan works for the time is
set in this parameter, so to burn the wood-pellet which is located in the burner's fire
chamber, before starts the maintain mode.
Manufacturer Advise:
60-240sec.
15.
MAXIMUM BURNER POWER
In this parameter the installer can set the maximum burner power, where the user can set
by visiting the burner's menu. This prevents the user to set the burner at a maximum
power, than the one it is required by the system.
Manufacturer Advise:
90kW
16.
MINIMUM BURNER POWER
In this parameter the installer can set the minimum burner power, where the user can set
by visiting the burner's menu. This prevents the user to set the burner at a maximum
power, than the one it is required by the system.
Manufacturer Advise:
19kW
17.
MINIMUM FURNACE TEMPERATURE
In this menu the manufacturer sets the minimal temperature of the furnace which can be
set by the user. The activity of the room thermostat causes the setting of the boiler into
this parameter. The minimal temperature of the boiler is set in the bracket of 20 to 60 °C.
Manufacturer Advise:
35
o
C
17