background image

   

8   

INSPECTION & CLEANING 

 
Check that the chimney is in good condition, dry and free from cracks and obstructions. The 
diameter of the chimney should not be less than 150mm and not more than 230mm. If any of 
these requirements are not met, the chimney should be lined by a suitable method. 
The chimney must be swept before connection to the fireplace. Where the chimney is believed 
to have previously served an open fire installation, it is possible that the higher flue gas 
temperature from the fireplace may loosen deposits that were previously firmly adhered, with 
the consequent risk of flue blockage. It is therefore recommended that the chimney be swept a 
second time within a month of regular use after installation. 
 
Assuming that when the fireplace is first installed, the chimney is clean, and sound, then the 
chimney flue should be inspected part way through the burning season to establish the 
regularity of sweeping required. If you have any doubts about the suitability of your chimney, 
consult your local dealer/stockiest. 
 
 

AIR FOR COMBUSTION 
 

Any room or space containing a fireplace should have a permanent air vent opening of at least 
the sizes shown in the table below. For fireplaces designed to burn “hardwood” solid fuels, the 
air supply should be designed to accommodate burning the fuel that produces the highest 
heating output. 
 

FIREPLACE   AIR   SUPPLIES   

      

Permanently   open   vents   as   below:   

      

      

      

If   design   air   permeability>5.0m3/(h.m2)   then   

Stove   with   no   flue   draught   

550mm2/kW   of   appliance   rated   output   above   5kW   

stabilizer   

      

      

If   design   air   permeability<5.0m3/(h.m2)   then   

      

550mm2/kW   for   balance   of   appliance   rated   output   

 

 

There must always be a permanent means of providing air for combustion into the room in 
which the fire is installed. A permanent vent with a total free area of at least 550mm2 for every 
kW rated above 5kW should be connected directly to the outside air or an adjacent room which 
itself has a permanent vent of the same size direct to the outside air

. The fitting of an 

extractor fan to either of these rooms is not permitted. 
 
 
CONNECTION TO THE CHIMNEY 

 
This MUST be carried out by an accredited/competent person and/or approved by your local 
authority before using the fireplace. 
 
Any existing flue must be in good condition with suitable access for collection and removal of 
debris.  
 
It is also important that suitable flue pipe complying with manufacturer recommendations is 
used to connect the fireplace to the chimney flue and that suitable access is provided into the 

Summary of Contents for Ambiante 700

Page 1: ...2 South Africa Tel 27 0 12 802 1515 ASSEMBLY OPERATING INSTRUCTIONS Important Read these instructions for use carefully so as to familiarize yourself with the appliance before connecting it to its gas container Keep these instructions for future reference Megamaster reserves the right to make changes to this manual without prior notice ...

Page 2: ...his user manual will render the guarantee null and void The following is not covered by this guarantee 1 Glass Panel 2 Rope and gasket seals 3 Paint discoloration irrespective of the period after purchase 4 Rust and rust related problems irrespective of the period after purchase 5 Fire Bricks Megamaster reserves the right to either repair or replace any fireplaces or components at their discretion...

Page 3: ...ys use a fireguard in the presence of children the elderly or the infirm DO NOT OVERFIRE it is possible to fire the fireplace beyond its design capacity This could damage the fireplace so watch for signs of over firing if any part of the fireplace starts to glow red the fireplace is in an over fire situation and the controls should be adjusted accordingly Never leave the fireplace unattended for l...

Page 4: ...ER direct any kind of liquid on to the fireplace particularly when it is hot 7 NEVER use gasoline or other flammable liquids for fire starting 8 NEVER use the fireplace to incinerate materials other than recommended fuels 9 NEVER carry out any modifications to this product If experiencing difficulty of any kind consult your local dealer 10 The installation of the fireplace and chimney MUST comply ...

Page 5: ...t 12mm thick if the fireplace is not to stand in a recess and has been tested to an applicable standard to verify that it cannot cause the temperature of the upper surface of the hearth to exceed 100o C Constructional hearths should be made of solid non combustible material such as concrete or masonry at least 125mm thick including the thickness of any non combustible floor and or decorative surfa...

Page 6: ...ld never be used Flue pipes must not project into the chimney connector such as to cause a restriction to the gas flow The minimum size for a masonry chimney not flue is 170mm in diameter A larger chimney size can affect the performance of the fireplace Liners should be installed in accordance with their manufacturers instructions Appropriate components should be selected to form the flue without ...

Page 7: ... the chimney See diagram below for effective flue height recommendations The outlet from a flue should be above the roof of the building in a position where the products of combustion can discharge freely and will not present a fire hazard whatever the wind conditions BENDS IN FLUES Offsets in flues are only acceptable if the following rules are respected a The chimney system shall have no more th...

Page 8: ...the sizes shown in the table below For fireplaces designed to burn hardwood solid fuels the air supply should be designed to accommodate burning the fuel that produces the highest heating output FIREPLACE AIR SUPPLIES Permanently open vents as below If design air permeability 5 0m3 h m2 then Stove with no flue draught 550mm2 kW of appliance rated output above 5kW stabilizer If design air permeabil...

Page 9: ... 6 inches in length Refer to the typical installation diagrams Fig 7 9 Flue connections must be well sealed A non combustible register plate minimum 1 5mm thick should be fitted to all installations between the flue and the building structure Fig 8 Horizontal register plate with top flue connection CLEANING THE FLUE Access for cleaning the flue should be incorporated in the system other than throu...

Page 10: ...nal advice Important Never fit an extractor fan in the same room as this fireplace USING YOUR FIREPLACE THE CONTROLS AIR SLIDE Moving the air slide to the left enables maximum air into the firebox Moving air slide to the right closes off air into the firebox which slows the burn down WARNING THE TEMPERATURE REACHED BY THESE ITEMS DURING OPERATION MAY CAUSE AN INJURY TO AN END USER AS THESE ARE INT...

Page 11: ...as to lay flat over the embers and logs of greater than 6 cm diameter should be split FIREBRICKS The firebricks are designed to fit in the base and along the rear and side walls of the firebox Please ensure the bricks are fitted before using the fire LIGHTING YOUR FIRE 1 Place firelighters and pieces of crumpled newspaper in firebox floor 2 Cover the paper with small diameter split kindling 3 Plac...

Page 12: ...ition NOTE This procedure can be done at any time for example in the morning so that the fire is still going later that day ASH REMOVAL Keep the fireplace free from a heavy buildup of ash The frequency of this is dependent upon the type and quality of fuel being used Ash should be removed before it builds up to the underside of the grate at which point the grate would be burning hot on both sides ...

Page 13: ...Stabilizer The fireplace has been recessed into the existing fireplace and a lot of heat is absorbed in the surrounding fireplace walls rather than being radiated into the room Pull the fireplace forward For the maximum efficiency of heat transference into the room the fireplace should be sited on the heart off the fireplace rather than recessed 3 The fireplace burns too fast Use whole logs rather...

Page 14: ...pected and maintained when in a cold condition NO unauthorized modification of this product should be carried out This fireplace requires regular maintenance by a competent person FIREPLACE BODY The fireplace is finished with a heat resistant paint which can be cleaned with a soft brush Wait until the fireplace has cooled down before doing this This finish can be renovated with heat resistant fire...

Page 15: ...ularly This means at least once a year for smokeless fuels and at least twice a year for wood and other fuels Only wire centered sweep s brushes fitted with a guide wheel should be used If it is not possible to sweep all parts of the chimney through the fireplace ensure there is adequate access to cleaning doors ...

Page 16: ..._______________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ____________________________________________________________________...

Reviews: