background image

13/12/2017 

System description

 

AGDS-2em 

The AGDS-2em system comprises of a mains powered main control panel capable of operating two sensors, either combustible 
or Carbon Monoxide gas or a mixture of both. The sensors are pre-calibrated by Medem (UK) Ltd such that they only require to 
be connected to the panel and functionally tested.  
 
In the event of a high alarm from one of the sensors the system will isolate the gas supply by closing a connected electric control 
valve. Emergency stop buttons and Thermal Links can be fitted and a fire alarm can close the gas valve when connected to the 
panel.  

Panel Buttons: 

 

Emergency stop button. 
Reset button 

Press and hold the reset button (2’s) when  power is first 
applied to enable gas. 

    Control Panel 

LED indications: 

 

Power On 

 

Green

 

High Alarm 

 

Flashing red 

 

High Alarm & Gas isolated

 

Permanent red

 

Low Alarm 

 

Flashing red (every second)

 

Gas On 

 

Yellow

 

EM Stop 

 

Yellow

 

Alert  

 

Yellow

 

Low Voltage Gas Detectors 

 

 
Combustible detectors are pre calibrated at 5% LEL (Pre alarm) and 10% LEL for the High alarm. 
Carbon Monoxide detectors are pre calibrated at 80ppm (pre alarm) and 100ppm for high alarm. 
 
Connect a detector to either the “detector 1 terminals”(

6

&

7

) or “detector 2 terminals”(

8

&

9

), each detector has a rotary address 

selector switch (0-F)  set to address 1 or 2 depending on which terminal has been used. Once connected and addressed you are 
required to enable the channel using the “channel enable switch”(

12

). 

 
Each sensor unit has an LED which shows green when power is applied.   
Note: There is a warm up period after initial power up of approximately 90 seconds. During this time the green LED will flash once 
per second and the output signal will be inhibited. This is to prevent spurious alarms. After the warm up period and on application 
of gas, the red LED will light when a high gas alarm level is reached. 
 
A detector incorrectly addressed or a channel enabled when not in use will cause a “sensor Alert state” (yellow LED 

20

); which 

indicates that a detector is not being recognised on the current setting’s - this can also be as a result of a connection issue with the 
wiring. 
 

When first powered or after a loss of power press and hold the reset button for 2 seconds to start the system and 
open the gas valve.  

Summary of Contents for AGDS-2em

Page 1: ...talled and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacture...

Page 2: ...the High alarm Carbon Monoxide detectors are pre calibrated at 80ppm pre alarm and 100ppm for high alarm Connect a detector to either the detector 1 terminals 6 7 or detector 2 terminals 8 9 each det...

Page 3: ...connection Reset 12 Enable Detectors Channels enable a channel when it has a detector connected 13 High alarm time delay function Controls the length of time between a High alarm and the closing of t...

Page 4: ...t be followed with reference to running low and mains voltage cables together The maximum cable length between a detector and the control panel should not exceed 100 metres if the distance between the...

Page 5: ...hould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indi...

Page 6: ...that is being monitored for See the gas detectors own instructions for more guidance All current wiring regulations must be followed with reference to running low and mains voltage cables together Th...

Page 7: ...g head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For addi...

Page 8: ...plier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will car...

Page 9: ...ctor 1 or detector 2 on the panel 5 Enable the detector channels 1 or 2 as being used by with switch 12 Connect the 3 amp fused spur 240 volt supply to marked terminals 6 Once power is connected to th...

Reviews: