background image

13/12/2017 

Main features

 

AGDS-2 

Power at 230 

volts from a 

3amp fused spur

 

Connections to panel: marked on board 

 
1. 

Live & Neutral 230 volts supply from 3amp switched fuse spur 

2. 

230 volts out to gas solenoid valve (5amp relay) 

3. 

Earth connection terminals 

4. 

High Alarm BMS relay (potential free contact, mains rated, max load 5amp) 

5. 

Remote emergency stop buttons SELV, multiple buttons connect in series  (requires a N/C circuit) 

6. 

Detector Channel One - Power connections for detectors, Methane, LPG, CO. 

7. 

Detector Channel One - Comms connections for detectors, Methane, LPG, CO. 

8. 

Detector Channel Two - Power connections for detectors, Methane, LPG, CO. 

9. 

Detector Channel Two - Comms connections for detectors, Methane, LPG, CO. 

10. 

Front Panel button connection - Mute 

11. 

Front Panel button connection - Reset 

12. 

Enable Detectors Channels - enable a channel when it has a detector connected. 

13. 

High alarm time delay function - Controls the length of time between a High alarm and the closing of the gas valve 

14. 

Jumper link to disable audible alarm sounder 

15. 

Power Led - will illuminate when mains power is applied to the system 

16. 

High Alarm LED - will illuminate when a detector enters high alarm (10% LEL for combustible 100ppm for CO) 

17. 

Low Alarm LED - will illuminate when a detector enters low alarm (5% LEL for combustible 80ppm for CO) 

18. 

Gas On LED - will illuminate to indicate when the gas valve is open - 

press and hold the reset button to open valve

 

19. 

EM Stop LED - will illuminate when any connected remote emergency stop buttons have been pressed 

20. 

Alert LED - will illuminate if comm’s to a detector are lost. 

(Check detector address and channel enable switch settings)

 

21. 

Front Panel button connection - Emergency Stop - not available on this model, (AGDS-2em only) 

 

Summary of Contents for AGDS-2

Page 1: ...alled and commissioned to the satisfaction of the manufacturer A commissioning certificate must be issued to the end user along with instructions for the operation of the equipment As the Manufacturer...

Page 2: ...gh alarm Carbon Monoxide detectors are pre calibrated at 80ppm pre alarm and 100ppm for high alarm Connect a detector to either the detector 1 terminals 6 7 or detector 2 terminals 8 9 each detector h...

Page 3: ...connection Reset 12 Enable Detectors Channels enable a channel when it has a detector connected 13 High alarm time delay function Controls the length of time between a High alarm and the closing of th...

Page 4: ...be followed with reference to running low and mains voltage cables together The maximum cable length between a detector and the control panel should not exceed 100 metres if the distance between the...

Page 5: ...ould be wired in series with the EM stop buttons To EM Stop connections in the panel Indicator bar shows when pressed Normal EM Stop Activated Multiple Stop Buttons Single Stop Buttons Resetting indic...

Page 6: ...s that is being monitored for See the gas detectors own instructions for more guidance AGDS 2 Detector Information VE supply Comm s From either the main panel Address Selector The selector must be set...

Page 7: ...ng head height and between 1m and 3m from the potential source Care should be taken so they are not located close to the edge of a canopy or in direct flow of the supply or extract ventilation For add...

Page 8: ...lier Medem UK will exchange faulty valves for return to the manufacturer 5 Where a Medem UK engineer or another company appointed by Medem UK commission and installed system then that system will carr...

Page 9: ...ector 1 or detector 2 on the panel 5 Enable the detector channels 1 or 2 as being used by with switch 12 Connect the 3 amp fused spur 240 volt supply to marked terminals 6 Once power is connected to t...

Reviews: