COMMERCIAL IN CONFIDENCE
MEC-PM-798 MEC Starter Kit ManualMEC-PM-798 MEC Starter Kit ManualMEC-
PM-798 MEC Starter Kit Manual
Page 23
420
Control
thermocouple
open-/short-
circuit
Thermocouple is
open- or short-
circuited.
Check thermocouple connection and polarity.
Check thermocouple wiring.
Is head very cold (less than 3 °C)?
If yes, warm up the head.
Emergency Shutdown,
Automatic Reset
(5 seconds)
421
Limit
thermocouple
open-/short-
circuit
Thermocouple is
open- or short-
circuited.
Check thermocouple connection and polarity.
Check thermocouple wiring.
Is head very cold (less than 3 °C)?
If yes, warm up the head.
Emergency Shutdown,
Automatic Reset
(5 seconds)
422
Control
thermocouple
integrity check
failure
Measured value not
rising during first
minute of burner
firing.
Check thermocouple temperature rise during first
minute of burner firing.
Check thermocouple is properly located in
thermal well.
Report to TDSP: provide logged data.
Emergency Shutdown,
Automatic Reset
(20 minutes)
423
Limit
thermocouple
integrity check
failure
Measured value not
rising during first
minute of burner
firing.
Check thermocouple temperature rise during first
minute of burner firing.
Check thermocouple is properly located in
thermal well.
Report to TDSP: provide logged data.
Emergency Shutdown,
Automatic Reset
(20 minutes)
424
Coolant over-
temperature
Coolant over-
temperature.
Check coolant flow rate.
Check coolant inlet temperature.
Report to TDSP: provide logged data.
Normal Shutdown,
Automatic Reset
(5 seconds)
425
Coolant under-
temperature
Coolant under-
temperature.
Check coolant flow rate.
Check coolant inlet temperature.
Report to TDSP: provide logged data.
Normal Shutdown,
Automatic Reset
(5 seconds)
501
Power meter
communications
checksum failure
Power meter
communications
checksum failure.
Internal communication problem.
Report to TDSP: provide logged data.
Normal Shutdown,
Automatic Reset
(3 minutes)
502
Power meter
communications
timeout
Power meter
communications
timeout.
Internal communication problem.
Report to TDSP: provide logged data.
Normal Shutdown,
Automatic Reset
(3 minutes)
503
Power meter
registration
timeout
Power meter
registration timeout.
Internal communication problem.
Report to TDSP: provide logged data.
Normal Shutdown,
Automatic Reset
(3 minutes)
504
VI protection
reset
VI protection
microcontroller has
reset.
Internal problem.
Report to TDSP: provide logged data.
Emergency Shutdown,
Automatic Reset
(3 minutes)
505
Under-voltage trip Grid voltage level is
too low.
Check grid voltage.
Emergency Shutdown,
Automatic Reset
(3 minutes)
506
Under-voltage trip Grid voltage level is
too low.
Check grid voltage.
Emergency Shutdown,
Automatic Reset
(3 minutes)
507
Under-voltage trip Grid voltage level is
too low.
Check grid voltage.
Emergency Shutdown,
Automatic Reset
(3 minutes)
508
Over-voltage trip
Grid voltage level is
too high.
Check grid voltage.
Emergency Shutdown,
Automatic Reset
(3 minutes)
509
Over-voltage trip
Grid voltage level is
too high.
Check grid voltage.
Emergency Shutdown,
Automatic Reset
(3 minutes)
510
Over-voltage trip
Grid voltage level is
too high.
Check grid voltage.
Emergency Shutdown,
Automatic Reset
(3 minutes)
511
Under-frequency
trip
Grid frequency is too
low.
Check grid frequency.
Emergency Shutdown,
Automatic Reset
(3 minutes)
512
Over-frequency
trip
Grid frequency is too
high.
Check grid frequency.
Emergency Shutdown,
Automatic Reset
(3 minutes)
513
Short-circuit trip
High current
measurement.
Check engine current.
Emergency Shutdown,
Automatic Reset
(3 minutes)