![Mebay ATS 420 User Manual Download Page 8](http://html.mh-extra.com/html/mebay/ats-420/ats-420_user-manual_1758463008.webp)
ATS 420 ATS CONTROLLER USER MANUAL
8
Closing S2 output
250V/10 AMP Non-contact normally Open output
AUX. OUTPUT 1
250V/5 AMP Non-contact normally Open output
AUX. OUTPUT 2\3
250V/10 AMP Non-contact normally Open output
Closing S1 input
Available if connecting with Battery -
Closing S2 input
Available if connecting with Battery -
AUX.INPUT 1\2
Available if connecting with Battery -
Working condition
-25-70
℃
Storage condition
-40-80
℃
Protection Level
IP54
:
when waterproof rubber gasket is added between
controller and its panel
Insulation strength
Apply AC 2.2kV voltage between high voltage terminal and
low voltage terminal; The leakage current is not more than
3mA within 1min.
Overall dimension
142mm*105mm*45mm
Panel cutout
116*90mm
Weight
0.5Kg
Overall Dimension and Wiring Diagram
Overall Dimension: