ATS 420 ATS CONTROLLER USER MANUAL
21
Prompt status information
The following is the prompt information and status display, also including
warning/alarm status
.
NO.
Item
Description
1
Please reset the
alarm
When there is fault alarm occurs, the indication will be
displayed when change the genset mode to Auto
Mode manually.
Show in status bar
2
S1 was already
closed
After S1 was already closed, the indication will be
displayed when "S2 close" button is pressed.
Show in status bar
3
S2 was already
closed
After S2 was already closed, the indication will be
displayed when "S1 close" button is pressed.
Show in status bar
4
Cycle Gen Start
Mode
Cycle Run Start Mode is active when "S1 Gens S2
Gens" system is active.
Show in status bar
5
Balance Gen Hours
Mode
Balance Run Start Mode is active when "S1 Gens S2
Gens" system is active.
Show in status bar
6
Master-Slave Gen
Start Mode
Master Run Start Mode is active when "S1 Gens S2
Gens" system is active.
Show in status bar
7
Auto Mode
Current mode is Auto mode.
Show in status bar
8
Manual Mode
Current mode is Manual mode.
Show in status bar
S1 Status (Upper to Lower)
No.
Item
Description
1
S1 Genset Fault
If there is “S1 fail to start” failure occurs when “S1
Gens S2 Gens” system is selected, it will initiate a fault
alarm. "
ALARM
" lights always on, displays "
S1
Genset Fault
" on the current fault screen.
2
S1 Fail to Close
In Auto mode, S1 close failure is occurs. "
ALARM
"
lights always on, displays "
S1 Failed to Close
" on
the current fault screen.
3
S1 Fail to Open
In Auto mode, S1 open failure is occurs. "
ALARM
"
lights always on, displays "
S1 Failed to Open
" on the
current fault screen.
4
S1 Over Voltage
Voltage is higher than the set value.
5
S1 Loss of Phase
Loss of any phase of A, B and C.
6
S1 Over Freq
Frequency is higher than the set value.
7
S1 Under Freq
Frequency has fallen below the set value.
8
S1 Under Volt
Voltage has fallen below the set value.
9
S1 Phase Seq
Wrong
A-B-C phase sequence is wrong
10
S1 Volt Normal
The S1 voltage is within the specified setting range