2.3 Product Dimensions
2.4 Mounting Requirements and Guidelines
ATTENTION
Make sure to follow the following mounting requirements
and guidelines when mounting the DTS 310.
When mounting the DTS 310 make sure to follow these guidelines:
Mount the DTS 310 as close as possible to the electrical panel being monitored.
Make sure that there is at least 4” of clearance above and below the DTS 310 for wiring and
connector clearance and ¼” of clearance on both sides for cooling.
Position the DTS 310 such that the labeling can be read from the upright position.
Only UL or ETL rated conduits and glands should be used.
It is recommended that two separate conduits be run for voltage and current connections.
User Supplied
UL or ETL certified 2A fast-blow fuses need to be installed between the Voltage
inputs of the DTS 310 and panel being monitored. Recommended Littelfuse BLS002 or equivalent.
14 to 12 AWG wire should be used for the voltage and ground with 300V or 600V insulation
depending on installation type and according to the table below.
A UL or ETL certified 600V circuit-breaker or fused disconnect must be installed within easy reach of
the DTS 310. The circuit-breaker or fused disconnect must be clearly marked as being
“the
disconnecting device”
for the DTS 310. See table below for the breaker and wire gauge to use.
WIRE & BREAKER GUIDE
Gauge of Wire
Recommended Breaker
14 AWG
15 Amp 600V 3-Pole Breaker
12 AWG
20 Amp 600V 3-Pole Breaker