Chapter 5
Specifications
Typical for 25°C unless otherwise specified.
Relay Specifications
Number 16
Contact Configuration
16 Form C
Contact Rating
6A @ 120VAC or 28VDC resistive
Contact Type
Gold overlay silver
Contact Resistance
100 milliohms max
Operate Time
20 milliseconds
Release Time
10 milliseconds max
Vibration
10 to 55 Hz (Dual amplitude 1.5mm)
Shock
10G (11 milliseconds)
Dielectric Isolation
500V (1 minute)
Life Expectancy
10 million mechanical operations, min
Isolated Inputs
Number 16
DC: ±28V
Voltage Range
AC: ±28V (50-1000Hz)
Input ‘High’ Level
>5V min (positive or negative input voltage - not TTL compatible)
Input ‘Low’ Level
<2.5V max (positive or negative input voltage)
Isolation 500V
Resistance
1.6k Ohms min
w/o filter: 20 µS
Response
w/ filter: 5 mS
Time constant: 5ms (200Hz)
Filter control: Each input individually programmable
Filters
Power-up /reset: Filters off
Power Consumption
All relays off
0.7A typical
Icc:
All relays on
2.0A typical
5-1