background image

SPECIFICATION

RSP-2400-12

MODEL

DC VOLTAGE

RATED CURRENT

CURRENT RANGE

RATED POWER

OUTPUT

VOLTAGE ADJ. RANGE

LINE REGULATION

LOAD REGULATION

SETUP, RISE TIME

HOLD UP TIME (Typ.)

VOLTAGE RANGE

FREQUENCY RANGE

EFFICIENCY (Typ.)

INPUT

INRUSH CURRENT (Typ.)

LEAKAGE CURRENT

OVER TEMPERATURE

OUTPUT VOLTAGE
PROGRAMMABLE(PV)

WORKING TEMP.

WORKING HUMIDITY

STORAGE TEMP., HUMIDITY

TEMP. COEFFICIENT

VIBRATION

MTBF

DIMENSION

OTHERS

NOTE

PACKING

OVERLOAD (OLP)

OVER VOLTAGE

AC CURRENT (Typ.)

12V

166.7A

0 ~ 166.7A

2000.4W

150mVp-p

10.8 ~ 13.2V

±

1.0%

±

0.5%

±

0.5%

1000ms, 80ms at full load

12ms at full load

180 ~ 264VAC          254 ~ 370VDC

47 ~ 63Hz

88%

15.5A/180VAC          12A/230VAC

60A/230VAC

<2.0mA / 240VAC

100 ~ 112% rated output power

13.8 ~ 16.8V

User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover

28.8 ~ 33.6V

57.6 ~ 67.2V

Protection type : Shut down o/p voltage, re-power on to recover

Shut down o/p voltage, recovers automatically after temperature goes down

-20 ~ +70

(Refer to "Derating Curve")

20 ~ 90% RH non-condensing

-40 ~ +85

, 10 ~ 95% RH

±

0.05%/

(0 ~ 50

)

10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes

234.1K hrs min.

Telcordia SR-332 (Bellcore) ; 83.9K hrs min.      MIL-HDBK-217F (25

)

278*177.8*63.5mm (L*W*H)

3.3Kg; 4pcs/14.2Kg/1.81CUFT

90.5%

91.5%

±

0.5%

±

0.5%

±

0.5%

±

0.5%

±

1.0%

±

1.0%

150mVp-p

22 ~ 28V

200mVp-p

43 ~ 56V

24V

100A

0 ~ 100A

2400W

48V

50A

0 ~ 50A

2400W

RSP-2400-24

RSP-2400-48

1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25  of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4. 

 

The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on 

  a 

mm*

mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives.

720

360

 For guidance on how to 

    perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

POWER FACTOR (Typ.)

0.95/230VAC at full load

SAFETY STANDARDS

UL60950-1, TUV EN60950-1 approved

RIPPLE & NOISE (max.)

Note.2

VOLTAGE TOLERANCE

Note.3

WITHSTAND VOLTAGE

ISOLATION RESISTANCE

I/P-O/P:3KVAC     I/P-FG:2KVAC     O/P-FG:0.5KVAC

I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25

/ 70% RH

ENVIRONMENT

SAFETY &

FUNCTION

EMC

(Note 4)

PROTECTION

2400W Power Supply with Single Output

R S P - 2 4 0 0

s e r i e s

ALARM SIGNAL OUTPUT

REMOTE ON-OFF CONTROL

AUXILIARY POWER

Please refer to the Function Manual

Power OK signal. Please refer to the Function Manual

[email protected](Only for Remote ON-OFF control)

Please refer to the Function Manual.

REMOTE SENSE

Compensate voltage drop on the load wiring up to 0.25V. Please refer to the Function Manual.

Parameter

Parameter

ESD

Radiated

EFT / Burst

Surge

Conducted

Magnetic Field

Voltage Dips and Interruptions

Conducted

Radiated

Harmonic Current

Voltage Flicker

EN55024 , EN61204-3, EN61000-6-2

Standard

Standard

EN55022 (CISPR22) / EN55011 (CISPR11)

EN55022 (CISPR22) / EN55011 (CISPR11)

EN61000-3-2

EN61000-3-3

EN61000-4-2

EN61000-4-3

EN61000-4-4

EN61000-4-5

EN61000-4-6

EN61000-4-8

EN61000-4-11

Test Level / Note

Test Level / Note

Level 3, 8KV air ; Level 2, 4KV contact

Level 3

Level 3

Level 3

Level 4

>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods

Class B

Class A

-----

-----

EMC IMMUNITY

EMC EMISSION

File Name:RSP-2400-SPEC   2016-07-26

4.8 ~ 28V

9.6 ~ 56V

2.4 ~ 13.2V

CURRENT SHARING

Up to 7200W or (2+1) units. Please refer to the Function Manual.

Level 3, 2KV/Line-Earth ; Level 2, 1KV/Line-Line

Summary of Contents for RSP-2400-12

Page 1: ...peed control working for the temperature up to 70 Moreover RSP 2400 provides vast design flexibility by equipping various built in functions such as the output programming active current sharing remote ON OFF control auxiliary power etc 24 RSP 2400 Series name Output wattage Output voltage 12V 24V 48V AC input 180 264VAC Built in active PFC function High efficiency up to 91 5 Forced air cooling by...

Page 2: ...The power supply is considered a component which will be installed into a final equipment All the EMC tests are been executed by mounting the unit on a mm mm metal plate with 1mm of thickness The final equipment must be re confirmed that it still meets EMC directives 720 360 For guidance on how to perform these EMC tests please refer to EMI testing of component power supplies as available on http ...

Page 3: ... T P O L P 76 78 80 82 84 86 88 90 92 10 20 30 40 50 60 70 80 90 100 2400W Power Supply with Single Output RSP 2400 series Derating Curve AMBIENT TEMPERATURE LOAD 20 40 60 50 80 100 20 0 10 20 30 40 50 60 70 HORIZONTAL Static Characteristics INPUT VOLTAGE V 60Hz 100 90 80 70 60 50 LOAD 180 185 190 195 200 210 220 230 240 250 264 MODEL INPUT 12V 2000 4W 2400W 2400W 166 7A 100A 50A 180 264VAC 24V 48...

Page 4: ...onents may be damaged and the power supply unit may thus be out of order The Remote Sense compensates voltage drop on the load wiring up to 0 25V 1 Remote Sense The rated current should change with the Output Voltage Programming accordingly MODEL PV Range 12V 2 4 13 2V 24V 4 8 28V 48V 9 6 56V Caution The power supply by factory default also the assumption for other sections is shipped with S V on ...

Page 5: ...tor likewise and OLP PIN9 OL SD PIN10 on CN3 are shorted when shipped Example 3 2 A Example 3 2 B Example 3 2 C SW Logic Power supply output ON SW Open SW Open SW Open Power supply output OFF SW Close SW Close SW Close 3 Remote ON OFF Remote ON OFF is activated by the configuration with respect to CN1 CN2 and CN3 as shown in the following diagram AUX 12V typ 12V typ 12V typ Internal Internal Inter...

Page 6: ...ut of alarm P OK Relay Contact Output of alarm P OK2 TTL Signal The signal turns to be High when the power supply is under 80 of the rated output voltage or say Power Fail High or open External applied voltage 500mA max High or open External applied voltage 10mA max R V Fig 4 2 Internal circuit of P OK2 Open collector method External voltage and R The max sink is 10mA and 30V P OK GND2 P OK2 R V 0...

Page 7: ...ent must not exceed the value determined by the following equation Maximum output current at parallel operation Rated current per unit Number of unit 0 9 File Name RSP 2400 SPEC 2016 07 26 2400W Power Supply with Single Output RSP 2400 series 1 Insert the shorting connector on CN3 that is shown in Fig 5 2 the Overload Protection Type will be constant current limiting with delay shutdown after 5 se...

Page 8: ...it 1 unit 2 unit 2 unit 2 unit 3 unit 3 unit 3 N1 N1 N1 L1 L1 L1 FG FG FG L2 L2 L2 N2 N2 N2 FG2 FG2 FG2 L3 L3 L3 N3 N3 N3 FG3 FG3 FG3 220V 380V 110V 190V Users can exploit three units of RSP 2400 unit 1 unit 2 unit 3 to work with 3 power system Please refer to following diagrams for configuration ψ File Name RSP 2400 SPEC 2016 07 26 2400W Power Supply with Single Output RSP 2400 series ...

Page 9: ...ounting Instruction Hole No Recommended Screw Size MAX Penetration Depth L Recommended mounting torque 1 5mm M4 Control Pin No Assignment HRS DF11 8DP 2DS or equivalent CN1 CN2 CN1 and CN2 are connected internally Mating Housing Terminal HRS DF11 8DS or equivalent HRS DF11 SC or equivalent 7 1 Kgf cm 0 Mounting Screw Mounting Surface Chassis of RSP 2400 L 1 1 1 1 1 1 Pin No 1 2 Function RCG RC Des...

Page 10: ...n Manual Please refer to http www meanwell com webnet search InstallationSearch html AC Input Terminal Pin No Assignment Pin No 1 3 2 Assignment Diagram M x a imum mounting torque 18Kgf cm AC L AC N FG 2 1 10 9 Control Pin No Assignment HRS DF11 10DP 2DS or equivalent CN3 Mating Housing Terminal HRS DF11 10DS or equivalent HRS DF11 SC or equivalent Pin No 1 2 Function P OK GND P OK Description Pow...