The recommended torque setting for terminals is shown as below. 

Model I/P 

O/P 

NDR-75 

6.9 kgf-cm (6 Lb-in) 

6.9 kgf-cm (6 Lb-in) 

NDR-120 

7.5 kgf-cm (6.5 Lb-in) 

7.5 kgf-cm (6.5 Lb-in) 

NDR-240 

7.5 kgf-cm (6.5 Lb-in) 

7.5 kgf-cm (6.5 Lb-in) 

NDR-480 

10.35 kgf-cm (9 Lb-in) 

10.35 kgf-cm (9 Lb-in) 

 
 

8

Suggested fuse and maximum number of the PSUs that can be connected to a circuit breaker at 230V are shown 

as below. 

Model Fuse 

Circuit breaker 

C16 D16 

NDR-75 T3.15A/L250V 6  13 

NDR-120 T4A/L250V 5  10 
NDR-240 T5A/L250V 4  10 
NDR-480 T8A/L250V 3  5 

9

Mounting Instruction

 

Mount as shown in figure only, with input terminals down, or else sufficient cooling will not be possible. 
Admissible DIN rail

TS35/7.5 or TS35/15 

For rail fastening

 

 

a

Tilt the unit slightly rearwards. 

b

Fit the unit over top hat rail. 

c

Slide it downward until it hits the stop. 

d

Press against the bottom for locking. 

e

Shake the unit slightly to check the locking action. 

 
 
 
 
 
 
 

 
 

 

10

For other information about the products, please refer to www.meanwell.com for details. 

 

 

Warning / Caution !! 

1

Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do 

not remove the case of the power supply by yourself! 

2

Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides 

together is not allowed. 

3

Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection! 

4

Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids. 

5

Only install the unit in a pollution degree 2 environment (Note.1).

 

6

Please do not install the unit in places with high moisture or near the water. 