background image

User Manual 

 

 

 

 

Type

 

 DIN rail power supply

 

 

 

EDR-120-24  INPUT

: 100-240VAC 2.6A 50/60Hz 

 

OUTPUT

: 24V 5A 

NDR-120-48  INPUT

: 100-240VAC 2.6A 50/60Hz 

OUTPUT

:  48V 2.5A 

 

NDR-240-48  INPUT

: 100-240VAC 2.8A 50/60Hz 

OUTPUT

: 48V 5A 

 

 

 

 

 

 

 

Introduction 

NDR is a DIN rail power supply series with an economical price and slim design. Like other Mean Well’s DIN series, 
they can be mounted on a TS35 Standard DIN rail. 

 

 

Installation 

1

) 

Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below,  

around the unit  in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the 
adjacent device is a  heat source. 

2

) 

The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and 

output on  the top. Mounting orientations other than that, such as upside down, horizontal, or table-
top mounting, is not  allowed. 

 

                   Use copper wire only, and recommended wires are shown as below. 
 
 
 
 
 
 
 

 
Make sure that all strands of each stranded wire enter the terminal connection and the screw 
terminals are  securely fixed to prevent poor contact. If the power supply possesses multi-output 
terminals, please make  sure each contact is connected to wires to prevent too much current stress on 
a single contact. 

AWG 18 

16 

14 

12 

Rated Current of 

Equipment (Amp) 

7A 10A  15A 

20A 

Cross-section of Lead(mm

2

 ) 

0.8 1.3  2.1 

3.3 

Note:  

Current each wire carries should be de-rated to 80% of the current suggested above when using 5 or more 
wires connected to the unit. 

 