Installation details
5.1 Installation place
5.1.1 Indoor Unit
a.
A place which provides the spaces around the indoor unit as required above in the
diagram.
b.
A place where is no obstacle near the inlet and outlet area.
c.
A place which can bear the weight of the indoor unit.
d.
A place which allows the air filter to be removed downward.
e.
A place where the reception range is not exposed to direct sunlight.
f.
In the center of the room where possible.
5.1.1.1 Please stand the unit in hard and flat ground;
Please reserve space for installation and maintenance.
5.1.1.2 Please check the elevation difference between the indoor unit and the outdoor
unit, the length of the refrigerant pipe, and the curved places (bend) of the pipe are no
more than the following numbers:
Elevation difference: no more than 10M(24K) or 15M(42K) (if the elevation
difference between indoor and outdoor unit is more than 10
or 15 meters, it is recommended that the indoor unit be
located higher than the outdoor unit.)
Pipe length: no more than 20M(24K) or 30M(42K)
Bends: no more than 3 places.
5.1.2 Outdoor Unit
5.1.2.1 Before installing the outdoor unit, you should:
a). Select a place where no direct sunlight or other heat-radioactivity may reach. A
sunshade is needed if it is unavoidable.
b). Select a place that is easy to connect indoor unit's pipe and electric wires.
c). Avoid a place where combustible gas may leak or stay.
d). Keep it in mind that water may drain out of the outdoor unit while in "Heat" mode.