Technical Manual Presence Detector SCN-P360XX.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
33
The
following
table
shows
the
available
settings:
ETS
‐
Text
Dynamic
range
[Default
value]
Comment
Settings
switching
behavior/Regulation
Constant
light
controlled
by
external
object
Presence
Adjustment
of
the
switch
on
behavior
Switch
on
control
delay
1s
– 5min
[5s]
Adjustment
of
the
delay
between
activation
and
start
of
regulation
Use
switch
on
dimming
value
Parameter
(select
dimming
value)
TeachIn
(teached
dimming
value)
Calculate
switch
on
value
Adjustment
of
the
power
up
value
Brightness
value
[Lux]
for
switch
on
use
last
dimming
setpoint
use
parameter
value
Adjustment
if
the
last
setpoint
shall
be
calculated
from
relative
dimming,
the
secenes
or
being
load
from
the
parameters
Use
day/night
object
not
used
use
for
next
switch
on
use
directly
and
for
next
switch
on
Activates
the
usage
oft
he
day/night
switchover.
At
activated
day/night
switchover,
two
setpoints
(day
and
night)
are
shown
otherwise
only
one
setpoint
is
shown
Preset
setpoint
at
day
100
– 750
Lux
[450
Lux]
Setpoint
for
day
mode
Preset
setpoint
at
night
100
– 750
Lux
[100
Lux]
Setpoint
for
night
mode
Settings
for
the
dimming
behavior
Cyclical
sending
of
dimming
value
not
used
12
s
‐
10
min
defines
the
time
for
the
cyclic
sending
of
the
dimming
value
Send
dimming
value
on
change
of
0
‐
20%
[2%]
defines
the
minimal
change
for
sending
the
dimming
value
CL
behavior
at
relative
dimming
use
new
dimming
value
Disable
CL
control
Adjsutment
if
regulation
stays
active
at
relative
dimming
Relative
dimming
time
5
– 60s
[20
s]
defines
the
time
for
dimming
from
0
to
100%
Table
16:
Settings
Constant
light
control
‐
1