Technical Manual Presence Detector SCN-P360XX.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
29
The
following
table
shows
the
available
settings
for
configuring
the
constant
level
light
regulation:
ETS
‐
Text
Dynamic
range
[Default
value]
Comment
Constant
light
control
disabled
enabled
Activation/Deactivation
of
the
constant
level
light
regulation
Control
out
sunlight
normal
few
very
few
defines
the
influence
of
the
solar
radiation
to
the
regulation
Selection
light
band
1
light
group
light
group
main
+
wall
light
group
main
+
window
light
group
main
+
wall
+
window
Selection
of
the
light
bands,
which
shall
be
controlled
Influence
proportional
wall
control
no
change
(x
1)
very
low
(x
1,2)
low
(x
1,4)
medium
(x
1,6)
high
(x
1,8)
very
high
(x
2)
defines
the
influence
of
the
light
group
wall
to
the
constant
level
light
regulation
Influence
proportional
window
control
no
change
(x
1)
very
low
(x
0,9)
low
(x
0,8)
medium
(x
0,7)
high
(x
0,6)
very
high
(x
0,5)
defines
the
influence
of
the
light
group
window
to
the
constant
level
light
regulation
Table
15:
General
settings
of
the
Constant
level
light
regulation
The
parameter
“Influence
proportional
zone
control”
indicates
the
influence
of
the
light
group
to
the
constant
light
control.
The
setting
“no
change”
(x
1)
switches
the
linearity
of
the
regulation
off
and
all
light
groups
light
always
with
the
same
brightness.
The
setting
“very
high”
(x
0,5
at
window
and
2
at
wall)
deactivates
means
that
the
difference
between
the
absolute
dimming
values
of
wall
and
window
is
very
high.
If
a
room
shall
be
controlled
via
the
constant
level
light
control,
it
is
recommended
to
use
the
TeachIn
function
to
get
best
results.
The
influences
of
the
light
groups
wall
and
window
must
be
adapted
to
the
specific
conditions
in
the
room.
Simplified
you
can
say
as
larger
the
room
as
greater
must
be
the
difference
of
the
controlling
parameter
to
1.
But
is
tis
recommended
to
check
the
parameters
always
locally
and
adapt
them
if
necessary.
The
regulation
can
be
aligned
via
the
parameter
“Control
out
sunlight”.
If
the
presence
detector
compensated
solar
radiation
too
strong,
the
value
of
this
parameter
should
be
set
to
few
or
very
few.
An
alternative
method
is
installing
the
presence
detector
more
into
the
middle
of
the
room.