2

 
 

Adjustment 
 

Electro-chemical  sensors  must  have  operated  for  approx.  1  hour  before  the  adjustment  can  be 
performed. 
The  calibration  gas  must  have  the  same  temperature  as  the  surrounding  area,  i.e.  the  same 
temperature as the sensor 
 
 

Measurement Equipment 
 

 

Voltmeter 0-2 V 

 

Screwdriver 

 

Zero gas (synthetic air) 

 

Calibration gas (C2H2 5000ppm) 

 

Gas supply equipment (flow regulator, flow meter 0-1 litre/minute) 

 

Gas supply pipe connection  

 
 
 
The adjustment is performed as follows: 

 
Zero balance 
 

The balance is performed at the sensor 

 

Unscrew the cap from the sensor 

-

 

Connect a digital voltmeter to the measurement pins “MP” (measurement range 0 - 2 V) 

Connect the testing pipe connector to the filter  

Add a zero gas concentration (synthetic air) 

The gas flow should be 0.5 litres/minute 

The gas temperature should have room temperature 

Now set the voltage with the trimmer “NP” to 0.04 V. 

 

   

 
 
 

4-20mA balance with calibration gas supply 
 

The balance is performed at the sensor 
 

Connect a digital voltmeter to the measurement pins “MP” (measurement range 0 - 2 V) 

Connect the calibration gas pipe connector to the filter  

Add a gas concentration (max. measurement range). 

The gas flow should be 0.5 litres/minute 

The gas temperature should have room temperature. 

Now set the voltage with the trimmer “V” to 0.2 V (Gas concentration = measurement range). 

 
 