background image

IM 671 / Page 10 of 28

Note: Heat pump models will generate condensate during
the heat season. To ensure that no condensation will run
down the building, always use a drain kit with heat pump.
Condensate drain kits can be supplied for internal and
external applications.
 Figure 14 illustrates the installation of
the indoor drain kit. The indoor drain kit should be installed
before placing the cabinet/wall sleeve into the opening. Install
as follows:
1.

Locate the drain so that it will be on the room side of the
wall when the cabinet/wall sleeve is installed.

2.

Drill a 

1

/

2

" (13mm) diameter hole in the base of the cabi-

net/wall sleeve for the drain line.

3.

Drill two (2) 

 5

/

32

" (4mm) pilot holes for the mounting screws.

These holes can be located using the drain kit as a pat-
tern.

4.

Assemble the drain kit as shown in figure 14 and securely
fasten it to the cabinet/wall sleeve with the screws provided.

5.

Slide the cabinet/wall sleeve into the opening and anchor
it into place.

Assembly of the external drain kit should be completed after
the cabinet/wall sleeve has been installed. Note: When using
the external drain kit, the sleeve must be flush or beynd the
outside finished wall - do not recess. Install the external drain
kit as follows:
1.

Assemble the drain kit as shown in figure 15.

2.

Choose which side of the cabinet/wall sleeve the drain kit
is to be installed.

3.

There are weep holes and pilot holes provided in the cabi-
net/wall sleeve from factory. Place the drain kit against
the chosen weep hole and fasten securely with screws
provided.

4.

Cover the unused weep holes with the block off plate sup-
plied with the drain kit.

Installation of Optional Condensate Drain Kit

Figure 14. Internal Drain K

it

Figure 15. External Drain Ki

t

Cover Plate

Tube

Gasket

Screws

Cover Plate

1/2" (13mm)

O.D.

Cabinet Bottom

Contractor To Drill Three (3) Holes To Accept Drain Kit

Square Drain Holes

Neoprene Sponge Gasket

Steel Mounting Plate

See Detail

Room Side

Note:

Use of 6" straight drain tube will require modification of
architectural louver.

Square Drain Holes

Neoprene Sponge Gasket

Steel Mounting Plate

Room Side

1

/

2

" (13mm) O.D. Drain Tube

Alternate 6" Long, 1/2" O.D. Straight Copper Tube

Summary of Contents for Suite II

Page 1: ...Installation Maintenance Data IM 671 1 Group PTAC Part Number 059490801 Date November 2003 Suite II PTAC PTHP Conditioner 1 Motor Standard 2 Motor Premium 2003 McQuay International...

Page 2: ...h the power supply available The Suite Series Comfort Conditioner is designed and built for through the wall installation in either new or existing buildings The self contained refrigerant sys tem del...

Page 3: ...e SHI Suite II 1 Motor Heat Pump IAQ DEI Suite II 2 Motor IAQ SHS Suite II 1 Motor Heat Pump DES Suite II 2 Motor SEA Suite II 1 Motor Automatic Damper DHA Suite II 2 Motor Heat Pump Automatic Damper...

Page 4: ...and units with hydronic heat See pages 5 6 7 9 for subbase dimensions Sides are adjustable 2 Opening needs to be 165 8 422mm x 425 8 1083mm when using a louver frame See page 8 Figure B of 3 76mm off...

Page 5: ...e C page 8 A 5 16 8mm hole is provided on each side 2 51 mm down from the top and 2 51 mm in from the rear of the cabinet wall sleeve Additional holes may be required to firmly secure the cabinet wall...

Page 6: ...he subbase of the cabi net wall sleeve Where a subbase is used secure wall sleeve to subbase with clips provided 6 Level cabinet wall sleeve in both directions and secure by anchoring with appropriate...

Page 7: ...to se cure firmly Caution Do not drill holes in the subbase of the cabinet wall sleeve Where a subbase is used secure wall sleeve to subbase with clips provided Wall Sleeve Installation Thick Wall Con...

Page 8: ...leeve Clean out weep holes to assure proper drainage 4 Attach indoor drain kit if used according to the instructions on page 10 Outdoor drain kits must be installed after wall sleeve is in place 5 Con...

Page 9: ...and includes the hydronic heating coil Refer to IM Bulletin 419 for installation details In addition rough in supply and return piping Electrical and plumbing rough in can be done through the back of...

Page 10: ...e external drain kit should be completed after the cabinet wall sleeve has been installed Note When using the external drain kit the sleeve must be flush or beynd the outside finished wall do not rece...

Page 11: ...r 4 screws packaged with the Tinnerman clips 15 Plug electrical cord into receptacle Excess cord for 208V and 230V units should be coiled neatly and stored in the conditioner Attach plug cord cover to...

Page 12: ...d into the receptacle During Start up applies only to standard equipment 1 Set manual ventilation damper to Open or Closed posi tion as required by owner 2 Select HIGH HEAT on the rotary switch Move t...

Page 13: ...clean operating or low usage conditions Unit malfunction will occur if air filters are not kept clean Rinse filter with hot water and a mild detergent Let dry and oil lightly to en hance dust collect...

Page 14: ...es on at the vari ous steps in this cycle can be a big help to the troubleshoot ing mechanic Figure 18 illustrates the refrigeration cycle The diagram shows what occurs in each component of a hermeti...

Page 15: ...Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e Windows and doors in room are open f Compressor not pumping indicated by 1 Low wattage 2 Condenser not war...

Page 16: ...apparent reason Inspection has revealed no loose components that might be the source of the noise Due to the action of the compressor it is possible to have internal noise develop if the refrigerant t...

Page 17: ...IM 671 Page 17 of 28 Wiring Diagram PTAC 1 Motor Standard Manual Changeover Control Model PSEA PSEC PSEH PSEI PSES Thermostat Unit Heat Electric Changeover Manual...

Page 18: ...IM 671 Page 18 of 28 Wiring Diagram Heat Pump 1 Motor Standard Manual Changeover Control Model PSHA PSHC PSHI PSHS Thermostat Unit Heat Electric Changeover Manual...

Page 19: ...IM 671 Page 19 of 28 Wiring Diagram Steam Heat with Normally Closed Valve 1 Motor Standard Manual Changeover Control Model PSEC PSEH PSES Thermostat Unit Heat Steam Changeover Manual...

Page 20: ...IM 671 Page 20 of 28 Wiring Diagram Hot Water Heat with Normally Open Valve 1 Motor Standard Manual Changeover Control Model PSEC PSEH PSES Thermostat Unit Heat Water Changeover Manual...

Page 21: ...IM 671 Page 21 of 28 Wiring Diagram PTAC 2 Motor Standard Manual Changeover Control Model PDEA PDEC PDEH PDEI PDES PFEC PFES Thermostat Unit Heat Electric Changeover Manual...

Page 22: ...IM 671 Page 22 of 28 Wiring Diagram Heat Pump 2 Motor Standard Manual Changeover Control Model PDHA PDHC PDHI PDHS PFHC PFHS Thermostat Unit Heat Heat Pump w Back up Electric Changeover Manual...

Page 23: ...IM 671 Page 23 of 28 Wiring Diagram Steam Heat with Normally Closed Valve 2 Motor Standard Manual Changeover Control Model PDEC PDEH PDES PFEC PFES Thermostat Unit Heat Steam Changeover Manual...

Page 24: ...IM 671 Page 24 of 28 Wiring Diagram Hot Water Heat with Normally Open Valve 2 Motor Standard Manual Changeover Control Model PDEH PDES PFEC PFES Thermostat Unit Heat Water Changeover Manual...

Page 25: ...IM 671 Page 25 of 28 NOTES...

Page 26: ...IM 671 Page 26 of 28 NOTES...

Page 27: ...IM 671 Page 27 of 28 NOTES...

Page 28: ...International www mcquay com 800 432 1342 IM 671 Rev 11 03 This document contains the most current product information as of this printing For the most up to date product information please go to www...

Reviews: