DC Inverter U-match Series Floor Ceiling Type Unit
28
WARNING!
①
. Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
②
. Match the terminal block numbers and connection cord colors with those of the indoor unit side.
Erroneous wiring may cause burning of the electric parts.
③
. Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
④
. Always fasten the outside covering of the connection cord with cord clamps. (If the insulator is not
clamped, electric leakage may occur.)
⑤
. Always connect the ground wire.
(4). Electric wiring between the indoor and outdoor units
Single-phase units (18/24K)
Single-phase units (18/24K)
MQIU-174018-MQS-174018-CFC216A
①
.
Power cord 3
×
1.5mm
2
(H07RN-F)
②
.
Power cord 3
×
1.0mm
2
(H05RN-F)
③
.
Communication Cords 2
×
0.75mm
2
(H05RN-F)
①
.
Power cord 3
×
2.5mm
2
(H07RN-F)
②
.
Power cord 3
×
1.0mm
2
(H05RN-F)
③
.
Communication cords 2
×
0.75mm
2
(H05RN-F)
Single-phase units (36~60K)
①
.
Power cord 3
×
2.5mm
2
(H07RN-F)
②
.
Power cord 3
×
1.0mm
2
(H05RN-F)
③
.
Communication cords 2
×
0.75mm
2
(H05RN-F)
①
.
Power cord 3
×
6.0mm
2
(H07RN-F)
②
.
Power cord 3
×
1.0mm
2
(H05RN-F)
③
.
Communication cords 2
×
0.75mm
2
(H05RN-F)
Fig. 4.29
(5). Electric wiring of indoor unit side
Remove the left cover plate and the electric box cover then insert the end of the
MQIU-174024-MQS-174024-CFC216A
MQIU-174036-MQS-174036-CFC216A
MQIU-174048-MQS-174048-CFC216A
MQIU-174060-MQS-174060-CFC216A